DIN Rail Power Supply

CliQ

12V 60W / DRP012V060W1AA

Highlights & Features

  • Universal AC input voltage
  • Power will not de-rate for the entire input voltage range
  • Power Boost of 150% for 3 seconds
  • Full corrosion resistant aluminium chassis
  • Hazardous Locations approval to ATEX and Class I, Div 2
  • Overvoltage / Overcurrent / Over Temperature / Short Circuit Protections
Dimensions (L x W x D) : 
121 x 32 x 120 mm
4.76" x 1.26" x 4.72"
Unit Weight : 
0.33 kg (0.73 lb)
Tags : ATEX ClassIDiv2
Nominal Output Voltage
12V
Output Current
5A
Output Voltage Adjustment Range
11-14Vdc
Output Power
60W
Line Regulation
< 0.5% typ. (@ 85-264Vac input, 100% input)
Load Regulation
< 1% typ. (@ 85-264Vac input, 0-100% input)
Start-up Time
< 2500ms @ nominal input (100% load, 25°C)
Hold-up Time
> 22ms @ 115Vac,
> 110ms @ 230Vac (100% load, 25°C)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
8,000µF Max
Nominal Input Voltage
100-240Vac
Input Voltage Range
85-264Vac 120-375Vdc
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
Input Current
< 1.35A @ 115Vac,
< 0.80A @ 230Vac
Efficiency at 100% load
> 86.0% @ 115Vac & 230Vac
Max Inrush Current
< 50A @ 115Vac,
< 100A @ 230Vac
Power Factor at 100% load
Conform to EN61000-3-2
Leakage Current
< 1mA @ 240Vac
Dimensions
121 x 32 x 120 mm
4.76" x 1.26" x 4.72"
Unit Weight
0.33 kg (0.73 lb)
Case Chassis / Cover
Aluminium
Cooling System
Convection
Operating Temperature
-20°C to +80°C
Storage Temperature
-25°C to +85°C
Power De-rating
> 50°C de-rate power by 2.5% /°C,
> 70°C de-rate by 4% /°C
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC60068-2-27, 30G (300m/S²) for a duration of 18ms
Vibration Test (Non-Operating)
IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); 90 min per axis for all X, Y, Z direction
Overvoltage
16V +10% / -5%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit
Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of Protection
IPX0
Protection Against Shock
Class I without Primary Earth connection
MTBF
> 500,000 hrs. as per Telcordia SR-332 I/P: 115Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
Electrical Safety
TUV to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), CB scheme to IEC 60950-1
CE
Inconformance with EMC directive 2014/30/EU and low voltage directive 2014/35/EU

In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
Galvanic Isolation
Input to Output: 4.0KVac,
Input to Ground: 1.5KVac,
Output to Ground: 1.5KVac
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355),
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2011
Class I, Division 2, Group A, B, C, D T4, Ta= -20°C to +80°C (> +50°C derating)

EN 60079-0:2012, EN 60079-15:2010 ( II 3G Ex nA IIC T4 Gc, Ta= -20°C to +80°C (> +50°C derating))
II 3 G ATEX 2014/34/EU
Certificate No. EPS 12 ATEX 1 491 X
Electrical Equipment for Use in Electrical Power Installations
EN 50178 / IEC 62103
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
CISPR 32, EN 55032, CISPR 11, EN 55011, FCC Title 47: Class B
Immunity
EN 55024, EN 61000-6-1, EN 61000-6-2
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3

Documents

Datasheet Uploaded on 30-Nov-2018 1.3 MB
.DXF Uploaded on 13-Jul-2015 131 KB
Manual Uploaded on 11-Nov-2016 1.5 MB
Mechanical Drawing Uploaded on 13-Jul-2015 55 KB
.STP Uploaded on 21-Jul-2015 1.9 MB
Image Uploaded on 03-Nov-2016 655 KB

Certificates

ATEX Uploaded on 20-Nov-2017 1.0 MB
CB Uploaded on 22-Jul-2016 231 KB
CE Uploaded on 24-Mar-2017 47 KB
CSA Uploaded on 20-Nov-2017 168 KB
EAC Uploaded on 28-Jul-2016 1.2 MB
Hazloc Uploaded on 13-Jul-2015 153 KB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
TUV Uploaded on 22-Jul-2016 658 KB
UL Uploaded on 21-Jul-2015 68 KB

Related Products

CliQ 24V 60W

DRP024V060W1AZ

-
Add to Comparison

Output Voltage

24V

Output Current

2.5A

Input Voltage

85-264 Vac

Dimensions

120.6 x 32 x 113 mm
4.75" x 1.26" x 4.45"

CliQ 24V 60W

DRP024V060W1AA

ATEX ClassIDiv2
Add to Comparison

Output Voltage

24V

Output Current

2.5A

Input Voltage

85-264 Vac

Dimensions

121 x 32 x 120 mm
4.76" x 1.26" x 4.72"

CliQ II 24V 60W

DRP024V060W1NY

Add to Comparison

Output Voltage

24V

Output Current

2.5A

Input Voltage

85-264 Vac

Dimensions

120.6 x 32 x 119.3 mm
4.75" x 1.26" x 4.70"

CliQ II 24V 60W

DRP024V060W1BA

Add to Comparison

Output Voltage

24V

Output Current

2.5A

Input Voltage

85-264 Vac

Dimensions

121 x 32 x 125 mm
4.76" x 1.26" x 4.92"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT