Panel Mount Power Supply

PMH

24V 150W / PMH-24V150WCDS

Highlights & Features

  • Household appliance approvals IEC/EN 60335-1, IEC/EN 61558-1 and IEC/EN 61558-2-16
  • Universal AC input voltage
  • Full power from -20°C to +50°C operation @ 5000m or 16400 ft. altitude
  • Full corrosion resistant aluminium casing
  • High MTBF > 700,000 hrs as per Telcordia SR-332
  • Versatile connector options available: IP20, Front Face and Harness connectors


Dimensions (L x W x D) : 
178 x 97 x 38 mm
7.01" x 3.82" x 1.50"
Unit Weight : 
0.56 kg (1.23 lb)
Nominal Output Voltage
24V
Output Voltage Adjustment Range
22-28Vdc
Output Current
6.25A
Output Power
150W
Line Regulation
< 0.5% (@ 85-264Vac input, 100% load)
Load Regulation
< 0.5% (@ 85-264Vac input, 0-100% load)
PARD (20MHz)
< 100mVpp
Start-up Time
100Vac:
< 2200ms (@ -20°C to 70°C) &
< 2500ms (@ < -20°C to -30°C)

240Vac:
< 1000ms (@ -30°C to 70°C)
Hold-up Time
> 40ms @ 115Vac, > 50ms 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 85-264Vac input, 0-100% load (Slew Rate: 0.1A/μS, 50% duty cycle @ 5Hz to 1KHz)
Start-up with Capacitive Loads
8,000μF Max (@ > -20°C, 85-264Vac input & @ ≤ -20°C, 100-264Vac input)
Rise Time
< 35ms @ nominal input (100% load)
Nominal Input Voltage
100-240Vac
Input Voltage Range
85-264Vac
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
DC Input Voltage Range
120-375Vdc
Input Current
< 1.60A @ 115Vac, < 0.90A @ 230Vac
Efficiency at 100% load
> 89.0% @ 115Vac, > 90.5% @ 230Vac
Max Inrush Current
(Cold Start)
< 30A @ 115Vac, < 60A @ 230Vac
Power Factor at 100% load
> 0.98 @ 115Vac, > 0.89 @ 230Vac
Leakage Current
< 0.75mA @ 240Vac
Max Power Dissipation
No Load: < 0.08W @ 115Vac & < 1.0W @ 230Vac
100% Load: 18.5W typ. @ 115Vac & 15.8W typ. @ 230Vac
Case Chassis / Cover
Aluminium
Dimensions
178 x 97 x 38 mm
7.01" x 3.82" x 1.50"
Unit Weight
0.56 kg (1.23 lb)
Indicator
Green LED (DC OK)
Cooling System
Convection
Operating Temperature
-30°C to +70°C
Storage Temperature
-30°C to +85°C
Power De-rating
-20°C to -30°C de-rate power by 2.0% / °C
> 50°C de-rate power by 2.5% / °C
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,1 times per direction, 2 times in total
Vibration Test (Non-Operating)
IEC 60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); displacement of 0.35mm; 20 min per axis for all X, Y, Z direction
Operating Altitude
0 to 5,000 Meters (16,400 ft.)
Pollution Degree
3
Bump Test (Operating)
IEC 60068-2-29, 10G (100m/S²) for a duration of 11ms,1000 times per direction, 6000 times in total
Over Voltage Category
II
Overvoltage
28.8-35.2V range, Hiccup Mode, Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 120% of rated load current, Hiccup Mode, Non-Latching (Auto recovery)
Over Temperature
< 75°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-recovery)
Short Circuit
Hiccup Mode, Non-Latching (Auto-recovery when the fault is removed)
Degree of Protection
IP20 (PMH-24V150WC☐U and PMH-24V150WC☐J)
Protection Against Shock
Class I with Primary Earth connection
MTBF
> 700,000 hrs. as per Telcordia SR-332
I/P: 115Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
Electrical Safety
SIQ Bauart: EN 60950-1, EN 60335-1, EN 61558-1, EN 61558-2-16
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
CB scheme: IEC 60950-1, IEC 60335-1, IEC 61558-1, IEC 61558-2-16
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
Galvanic Isolation
Input to Output: 4.5KVac
Input to Ground: 1.5KVac

Output to Ground:
Output non-isolated to PE (common pins connect to PE) (PMH-24V150WC☐A, PMH-24V150WC☐J, PMH-24V150WC☐L, PMH-24V150WC☐H)
1.5KVdc (Output isolated to PE) (PMH-24V150WC☐S, PMH-24V150WC☐U, PMH-24V150WC☐V, PMH-24V150WC☐T)
Safety Entry Low Voltage
Output non-isolated to PE: PELV (EN 60335), SELV (EN 60950)
Output isolated to PE: SELV (EN 60335), SELV (EN 60950)
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
(CE & RE)
EN 55011, CISPR 32, EN 55032, FCC Title 47: Class B, EN 55014-1, EN 61000-6-3
Immunity
EN 55024, EN 61000-6-2, EN 55014-2
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3

Documents

Datasheet Uploaded on 27-Nov-2018 1.3 MB
.DXF Uploaded on 22-May-2018 1.2 MB
Manual Uploaded on 01-Aug-2018 1.3 MB
Mechanical Drawing Uploaded on 21-May-2018 342 KB
.STP Uploaded on 22-May-2018 12.8 MB
Image Uploaded on 18-May-2018 397 KB

Certificates

CB Uploaded on 21-May-2018 1.9 MB
CE Uploaded on 21-May-2018 141 KB
EAC Uploaded on 28-Jul-2016 1.2 MB
REACH Uploaded on 23-Jul-2018 6.9 MB
RoHS Uploaded on 16-Feb-2018 5.5 MB
SIQ Uploaded on 21-May-2018 591 KB
UL Uploaded on 20-Dec-2017 68 KB
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT