(Enclosure to Neutral) 0.50mA / 1.21mA @ 110Vac, 50Hz, TN/TT system / IT system 0.71mA / 1.73mA @ 132Vac, 50Hz, TN/TT system / IT system 1.18mA / 2.82mA @ 264Vac, 50Hz, TN/TT system / IT system
Vertical Mounting: Temperature: > 60°C de-rate power by 2.5% / °C Input Voltage: If < 90Vac, > 55°C de-rate power by 1.67% / °C Horizontal Mounting: Temperature: > 40°C de-rate power by 1.67% / °C Input Voltage: If < 90Vac, > 35°C de-rate power by 1.43% / °C
Luftfeuchtigkeit Betrieb
5 to 95% RH (Non-Condensing)
Stoßtest (außer Betrieb)
IEC 60068-2-27, Half Sine Wave: 30G for a duration of 18ms; 3 times per direction, 6 times in total
Vibration (außer Betrieb)
IEC 60068-2-6, Sine Wave: 10-500Hz; 3G peak; displacement of 0.35mm; 60 min per axis for all X, Y, Z directions
Luftfeuchtigkeit (Lagerung)
-
Einsatzhöhe
0 to 5,000 Meters (16,400 ft.) 0 to 2,500 Meters (8,200 ft.) for IEC/EN 61558
Verschmutzungsgrad
2
Stoßtest (Betrieb)
IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
Überspannungskategorie
III According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part)
Corrosion
-
Überspannung
< 32V, SELV Output, Hiccup Mode, Non-Latching (Auto- Recovery)
SIQ Bauart: EN 62368-1, EN 61558-1, EN 61558-2-16, EN 61010-1, EN 61010-2-201 UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1, IEC 61558-1, IEC 61558-2-16, IEC 61010-1, IEC 61010-2-201 UKCA: BS EN 62368-1, BS EN 61558-1, BS EN 61558-2-16, BS EN 61010-1, BS EN 61010-2-201
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
Medizinische Unbedenklichkeit
-
Galvanische Trennung
Input / Output: 4.54KVac Input / PE: 2.5KVac Input / DC OK relay contact: 4.54KVac (Recommend to connect DC OK pins together with output pins) Output / PE: 1.5KVac Output / DC OK relay contact: 0.5KVac DC OK relay contact / PE: 1.5KVac
Industrielle Steuerungen
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355) CSA: CSA C22.2 No. 107.1-01 (File No. 181564)
Gefahrenbereich/ ATEX
-
II 3 G ATEX 2014/34/EU
-
Elektrische Ausrüstung an Maschinen
EN/BS EN 60204-1 (over voltage category III)
Elektrische Ausrüstung zum Einsatz in Stromversorgungsanlagen
IEC/EN/BS EN 62477-1 / IEC 62103
Sicherheit Eingang Niederspannung
SELV (IEC 60950-1)
Maritim
DNV GL: Germanischer Lloyd classified ABS: American Bureau for Shipping) PDA Environmental category: C, EMC2
Material und Teile
-
Isolationswiderstand
> 5MOhm (Input to Output, 500Vdc)
PE-Widerstand
< 0.1Ohm
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
Certificates for Other Countries
-
BIS
-
KC
-
Electrical Equipment for Measurement, Control, and Laboratory Use
-
ITE Safety
-
SIL3
-
Emission
(CE & RE) Generic Standards: EN/BS EN 61000-6-3 CISPR 32, EN/BS EN 55032, KN 32, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B
Störfestigkeit
Generic Standards: EN/BS EN 55024, KN 35, EN/BS EN 61000-6-2
Seien Sie mit der/die erste um über neue Veranstaltungen, Neuigkeiten und Produkte informiert zu werden!
Melden Sie sich jetzt für unseren Newsletter an
Seien Sie mit der/die erste um über neue Veranstaltungen, Neuigkeiten und Produkte informiert zu werden!
Abonnieren
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Datenschutzerklärung.
Marketing Permissions*
DeltaPSU will use the information you provide on this form to be in touch with you.
To unsubscribe, click the link in our newsletter. We will treat your data with respect.
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Datenschutzerklärung. Accept