24V
240W
10A
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase)
124 x 60 x 117 mm
4.88” x 2.36” x 4.61”
0.81 kg (1.79 lb)
24V
240W
10A
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase)
124 x 60 x 117 mm
4.88” x 2.36” x 4.61”
0.81 kg (1.79 lb)
Output Current
10A
|
Output Voltage
24V
|
Output Voltage Range
|
Output Voltage Adjustment Range
24-28Vdc
|
Output Power
240W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
< 0.5% (@ 200-550Vac input, 100% load)
|
Load Regulation
< 1.0% (@ 200-550Vac input, 0-100% load)
|
PARD
< 150mVpp @ -10°C and above
< 200mVpp @ below -10°C |
Start-up Time
< 1,000ms @ nominal input (100% load)
|
Hold-up Time
> 18ms @ 2 x 230Vac,
> 30ms @ 2 x 400Vac (100% load) |
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 180-550Vac input, 0-100% load
(Slew Rate: 0.1A/μs, 50% duty cycle @ 5Hz) |
Start-up with Capacitive Loads
10,000µF Max
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
-
|
Power Boost Duration
-
|
Power Boost Recovery Time
-
|
Nominal Input Voltage
2 x 200-500Vac (2-Phase)
200-277Vac (Single Phase) |
Input Voltage Range
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase) |
Max Input Voltage
-
|
Nominal Input Frequency
50-60Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
|
DC Input Voltage Range
254-780Vdc
|
Input Current
< 2.00A @ 2 x 230Vac,
< 1.00A @ 2 x 400Vac |
Input Power (Standby Mode)
-
|
Efficiency at 100% load
> 90.0% @ 2 x 400Vac
|
Max Inrush Current
< 50A @ 2 x 200Vac & 2 x 500Vac
|
Charging Time
-
|
Power Factor at 100% load
-
|
Leakage Current
< 3.5mA @ 500Vac
|
Nominal Current
-
|
Total Harmonic Distortion
-
|
Max Power Dissipation
0% load: < 8.5W @ 2 x 200Vac, < 9.5W @ 2 x 500Vac
100% load: < 26.5W @ 2 x 200Vac, < 21.5W @ 2 x 500Vac |
Case Chassis / Cover
Aluminium
|
|
Indicator
Green LED (DC OK)
|
|
Cooling System
Convection
|
|
Input Terminal
3 Pins (Rated 600V/35A)
|
|
Output Terminal
4 Pins (Rated 300V/28A)
|
|
Signal Terminal
-
|
|
Noise Sound Pressure Level (SPL)
< 40dBA
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
|
|
Wire
Input: AWG 18-8
Output: AWG 16-12 (ensure that all output terminals are connected) |
|
Protection Structure
-
|
|
Terminal
-
|
|
Unit Weight
0.81 kg (1.79 lb)
|
Dimensions
124 x 60 x
117 mm
4.88” x 2.36” x 4.61” |
Vibration (Operating)
-
|
Shock Test (Operating)
-
|
Operating Temperature
-30°C to +70°C
|
Storage Temperature
-40°C to +85°C
|
Power De-rating
Vertical: > 50°C de-rate power by 2.25% / °C
Horizontal: > 30°C de-rate power by 2% / °C Input Voltage: < 200Vac de-rate power by 0.5% / Vac |
Operating Humidity
5 to 95% RH (Non-Condensing)
|
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
1 times per direction, 2 times in total |
Vibration (Non-Operating)
IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);
60 min per axis for all X, Y, Z direction |
Storage Humidity
-
|
Operating Altitude
0 to 2,500 Meters (8,200 ft.) for ITE application (@ 50°C)
0 to 2,000 Meters (6,560 ft.) for Industrial application (@ 50°C) |
Pollution Degree
2
|
Bump Test (Operating)
IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
|
Over Voltage Category
III
According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part) |
Overvoltage
32V ±10%, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery)
|
Overload / Overcurrent
> 120-180% of rated load current, Constant current, Hiccup Mode (Auto-Recovery)
|
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Reverse Polarity Protection
-
|
Degree of Protection
IP20
|
Protection Against Shock
Class I with Primary Earth connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
Internal Fuse
-
|
Insufficient Input Voltage Protection
-
|
MTBF
> 500,000 hrs. as per Telcordia SR-332 (I/P: 2 x 200Vac & 500Vac, O/P: 100% load, Ta: 25°C)
|
Expected Cap Life Time
10 years (2 x 200Vac & 500Vac, 50% load @ 40°C)
|
Safety Certificate
-
|
Electrical Safety
SIQ Bauart: EN 62368-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1 UKCA: BS EN 62368-1 |
CE
In conformance with EMC Directive 2014/30/EU (only AC input) and Low Voltage Directive 2014/35/EU
|
Medical Safety
-
|
Galvanic Isolation
Input to Output: 4.0 KVac
Input to Ground: 2.0 KVac Output to Ground: 1.5 KVac |
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA: CSA C22.2 No. 107.1-01 (File No. 181564) |
Hazardous Location / ATEX
-
|
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
EN/BS EN 60204-1 (over voltage category III)
|
Electrical Equipment for Use in Electrical Power Installations
IEC/EN/BS EN 62477-1 / IEC 62103
|
Safety Entry Low Voltage
SELV (IEC 60950-1)
|
Maritime
-
|
Material and Parts
-
|
Isolation Resistance
-
|
PE Resistance
-
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
Certificates for Other Countries
-
|
BIS
-
|
KC
-
|
Emission
(CE & RE)
Generic Standards: CISPR 32, EN/BS EN 55032, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B |
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
EN/BS EN 61204-3
|
48V
480W
10A
90-264 Vac
24V
480W
20A
90-264 Vac
12V
120W
10A
90-264 Vac
24V
480W
20A
90-264 Vac
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Privacy Policy.
DeltaPSU will use the information you provide on this form to be in touch with you.
To unsubscribe, click the link in our newsletter. We will treat your data with respect.