Click the link below to download the file.
Get your files as below link
Dowload link
48V
600W
12.5A
85-264Vac
215 x 120 x 61 mm
8.46” x 4.72” x 2.40”
1.54 kg (3.40 lb)
48V
600W
12.5A
85-264Vac
215 x 120 x 61 mm
8.46” x 4.72” x 2.40”
1.54 kg (3.40 lb)
Output Current
12.5A
|
Output Voltage
48V
|
Output Voltage Range
|
Output Voltage Adjustment Range
43.2-52.8Vdc
|
Output Power
600W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
<192mV (@115-264Vac input, 100% load)
|
Load Regulation
<300mV (@115-264Vac input, 100% load)
|
PARD
<300mVpp
|
Start-up Time
<500ms @115Vac & 230Vac (100% load)
|
Hold-up Time
<20ms @115Vac & 230Vac (100% load)
|
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 115-264Vac input, 10-100%
Slew Rate: 0.1A/µs, 50% duty cycle @ 5Hz to 1kHz) |
Start-up with Capacitive Loads
10,000µF Max
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
<100ms @115Vac & 230Vac (100% load)
|
Power Boost Duration
-
|
Power Boost Recovery Time
-
|
Nominal Input Voltage
100-240Vac
|
Input Voltage Range
85-264Vac
|
Max Input Voltage
-
|
Nominal Input Frequency
50-60Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
test
|
DC Input Voltage Range
120-375Vdc
|
Input Current
<6.50A @115Vac, <3.20A @230Vac
|
Input Power (Standby Mode)
-
|
Efficiency at 100% load
>87% @115Vac, >90% @230Vac
|
Max Inrush Current
<20A @ 115Vac & <40A @ 230Vac
|
Charging Time
-
|
Power Factor at 100% load
>0.98 @ 115Vac, >0.96 @ 230Vac
|
Leakage Current
< 3.0 mA / 4.0 mA @ 264 Vac
|
Nominal Current
-
|
Total Harmonic Distortion
-
|
Max Power Dissipation
-
|
Efficiency @ 10% load
-
|
Case Chassis / Cover
SECC
|
|
Indicator
Green LED DC OK
|
|
Cooling System
Forced Cooling (Built-in Fan)
|
|
Input Terminal
M3.5 x 3 Pins (Rated 300V/20A)
|
|
Output Terminal
M3.5 x 4 Pins (Rated 300V/25A)
|
|
Signal Terminal
-
|
|
Noise Sound Pressure Level (SPL)
<52dBA
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
-
|
|
Wire
Input AWG 14-12
|
|
Protection Structure
-
|
|
Terminal
-
|
|
Unit Weight
1.54 kg (3.40 lb)
|
Dimensions
215 x 120 x
61 mm
8.46” x 4.72” x 2.40” |
Vibration (Operating)
-
|
Shock Test (Operating)
-
|
Operating Temperature
-20°C to +70°C
|
Storage Temperature
-40°C to +85°C
|
Power De-rating
> 50°C de-rate power by 2.5% / °C
|
Operating Humidity
5 to 95% RH (Non-Condensing)
|
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S² for a duration of 18ms
1 times per direction, / 2 times in total |
Vibration (Non-Operating)
IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak);
displacement of 0.35mm; 20 min per axis for all X,Y,Z |
Storage Humidity
-
|
Operating Altitude
0 to 3,000 Meters (9,840 ft.)
|
Pollution Degree
2
|
Bump Test (Operating)
-
|
Over Voltage Category
II
|
Overvoltage
<69.3V, SELV Output, Latch Mode
|
Overload / Overcurrent
>150% of rated load current, Hiccup Mode,
Non-Latching (Auto-Recovery) |
Over Temperature
< 80°C Surrounding Air Temp@ 100% load, Latch Mode
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-recovery when the fault is removed).
|
Reverse Polarity Protection
-
|
Degree of Protection
-
|
Protection Against Shock
Class I with PE* connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
Internal Fuse
-
|
Insufficient Input Voltage Protection
-
|
MTBF
>700,000 hrs. as per Telcordia SR-332
I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C |
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C
|
Safety Certificate
-
|
Electrical Safety
SIQ Bauart: EN 62368-1
UL/cUL recognized UL60950-1 and CSA C22.2 No. 60950-1, UL 62368-1 and CSA C22.2 No. 62368-1 CB scheme IEC 60950-1, IEC 62368-1 |
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
Medical Safety
-
|
Galvanic Isolation
Input to Output: 3.0KVac
Input to Ground: 2.0Kvac Output to Ground: 0.5KVac |
Industrial Control Equipment
-
|
Hazardous Location / ATEX
-
|
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
-
|
Electrical Equipment for Use in Electrical Power Installations
-
|
Safety Entry Low Voltage
SELV (IEC 60950-1)
|
Maritime
-
|
Material and Parts
-
|
Isolation Resistance
-
|
PE Resistance
-
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and
The Electromagnetic Compatibility Regulations 2016 No. 1091 |
Certificates for Other Countries
-
|
BIS
-
|
KC
-
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
ITE Safety
-
|
Emission
Generic Standards: CISPR 32, EN/BS EN 55032, CISPR 11, EN/BS EN 55011, FCC Title 47,
VCCI: Class B |
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 61000-6-2
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
-
|
48V
240W
5A
90-264 Vac
48V
320W
6.7A
90-264 Vac
24V
320W
13.4A
90-264 Vac
12V
240W
20A
90-264 Vac
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Privacy Policy.
DeltaPSU will use the information you provide on this form to be in touch with you.
To unsubscribe, click the link in our newsletter. We will treat your data with respect.