DIN Rail Power Supply

Lyte

24V 480W / DRL-24V480W1AS

Highlights & Features

  • Universal AC input voltage
  • Built-in constant current circuit for reactive loads
  • Up to 88.0% efficiency
  • Full power from -20°C to +50°C operation at 230Vac @ 5000 meters or 16400 feet altitude
  • Built-in DC OK relay contact option available
  • Compliance to SEMI F47 @ 200Vac
  • Conformal coating on PCBAs to protect against common dust and chemical pollutants


Dimensions (L x W x D) : 
123.6 x 85.5 x 128.5 mm
4.87" x 3.37" x 5.06"
Unit Weight : 
1.30 kg (2.87 lb)
Nominal Output Voltage
24V
Output Current
20A
Output Voltage Adjustment Range
22-28Vdc
Output Power
480W
Line Regulation
< 0.5% (@ 85-264Vac, 100% load)
Load Regulation
< 1.5% (0-100% load)@ > -10°C to +70°C
< 2.0% ( 0-100% load) @ ≤ -10°C to -20°C
PARD
< 120mVpp @ > -10°C to +70°C
< 240mVpp @ ≤ -10°C to -20°C
Start-up Time
1000ms typ.@ 115Vac & 230Vac (100% load)
Hold-up Time
10ms typ.@ 115Vac (100% load)
16ms typ.@ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 10% (2400mVpp) @ 85-264Vac input, 0-50% load, 50-100% load (Slew Rate: 0.1A/μs)
Start-up with Capacitive Loads
8,000µF Max
Rise Time
100ms typ. @ nominal input (100% load)
Nominal Input Voltage
100-240Vac
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
DC Input Voltage Range
120-375Vdc
Input Current
5.4A typ.@115Vac, 2.7A typ.@ 230Vac
Efficiency at 100% load
85% typ. @ 115Vac, 88% typ. @ 230Vac
Max Inrush Current
40A typ.@115Vac, 80A typ.@ 230Vac
Power Factor at 100% load
> 0.95 @ 115Vac & 230Vac
Leakage Current
< 1mA @ 264Vac
Dimensions
123.6 x 85.5 x 128.5 mm
4.87" x 3.37" x 5.06"
Unit Weight
1.30 kg (2.87 lb)
Case Chassis / Cover
SGCC / Aluminium
Indicator
Green LED (DC OK)
Cooling System
Convection
Operating Temperature
-20°C to +70°C
Storage Temperature
-40°C to +85°C
Power De-rating
> 40°C de-rate power by 1.67% / °C @ 115Vac (90-229Vac)
> 50°C de-rate power by 2.5% / °C @ 230Vac (230-264Vac)
< 100Vac de-rate power by 1% / Vac
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, 27, Half Sine Wave: 50G for duration of 22ms; 3 times per direction, 9 times in total
Shock (Operating)
IEC 60068-2-27, 27, Half Sine Wave: 4G for duration of 22ms; 3 time per direction, 9 times in total
Vibration Test (Non-Operating)
IEC 60068-2-6, Random: 5Hz to 500Hz; 2.09Grms; 20 min per axis for all X, Y, Z directions
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6m/s² (2G peak); displacement of 0.35mm; 10 min per cycle, 60 min for all X, Y, Z direction
Operating Altitude
0 to 5,000 Meters (16,400 ft.) for ITE application
0 to 2,000 Meters (6,560 ft.) for ICE application
Pollution Degree
2
Overvoltage
28.8V-35.2V, SELV Output, Latch Mode
Overload / Overcurrent
109-130% of rated load current, Continuous current
Over Temperature
Latch Mode
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of Protection
IP20
Protection Against Shock
Class I with Primary Earth connection
MTBF
Telcordia SR-332: > 700,000 hrs
I/P: 100Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
Electrical Safety
TUV Bauart: EN 60950-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881)
CCC: GB4943.1
CB scheme: IEC 60950-1
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
Galvanic Isolation
Input to Output: 3.0KVac
Input to Ground: 2.0KVac
Output to Ground: 0.5KVac
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E338991)
Safety Entry Low Voltage
SELV (EN 60950-1)
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
(CE & RE)
Generic Standards: EN 61000-6-3, EN 61000-6-4
CISPR 32, EN 55032, EN 55011, FCC Title 47: Class B; GB9254.1
Immunity
Immunity to: Generic Standards: EN 61000-6-1, EN 61000-6-2, EN 55024
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A; GB17625.1
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
Component Power Supply for General Use
EN 61204-3

Documents

Datasheet Uploaded on 22-Apr-2019 1.0 MB
.DXF Uploaded on 05-May-2016 726 KB
Manual Uploaded on 29-Apr-2016 3.2 MB
Mechanical Drawing Uploaded on 04-May-2016 40 KB
.STP Uploaded on 05-May-2016 1.4 MB
Image Uploaded on 03-Nov-2016 157 KB

Certificates

CB Uploaded on 29-Apr-2016 294 KB
CCC Uploaded on 04-May-2016 922 KB
CE Uploaded on 26-Apr-2017 115 KB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
TUV Uploaded on 04-May-2016 453 KB
UL Uploaded on 05-Apr-2019 774 KB

Related Products

Lyte 24V 120W

DRL-24V120W1AS

Add to Comparison

Output Voltage

24V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

123.6 x 40 x 117.6 mm
4.87" x 1.57" x 4.63"

Lyte 48V 120W

DRL-48V120W1AS

Add to Comparison

Output Voltage

48V

Output Current

2.5A

Input Voltage

0-0 Vac

Dimensions

123.6 x 40 x 117.6 mm
4.87" x 1.57" x 4.63"

Lyte 24V 240W

DRL-24V240W1AS

Add to Comparison

Output Voltage

24V

Output Current

10A

Input Voltage

0-0 Vac

Dimensions

123.6 x 60 x 117.6 mm
4.87" x 2.36" x 4.63"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT