DIN Rail Power Supply

Lyte

48V 120W / DRL-48V120W1AS

Highlights & Features

  • Universal AC input voltage
  • Built-in constant current circuit for reactive loads
  • Up to 88.0% efficiency
  • Full power from -10°C to +50°C operation at 230Vac @ 5000 meters or 16400 feet altitude
  • Built-in DC OK relay contact option available
  • Compliance to SEMI F47 @ 200Vac
  • Conformal coating on PCBAs to protect against common dust and chemical pollutants


Dimensions (L x W x D) : 
123.6 x 40 x 117.6 mm
4.87" x 1.57" x 4.63"
Unit Weight : 
0.54 kg (1.19 lb)
Nominal Output Voltage
48V
Output Current
2.5A
Output Voltage Adjustment Range
44-56Vdc
Output Power
120W
Line Regulation
< 0.5% (@ 85-264Vac, 100% load)
Load Regulation
< 1% (0-100% load)
PARD
< 150mVpp @ > -10°C to +70°C
< 300mVpp @ ≤ -10°C to -20°C
Start-up Time
200ms typ. @ 115Vac & 230Vac (100% load)
Hold-up Time
20ms typ. @ 115Vac (100% load)
90ms typ. @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 10% @ 85-264Vac input, 0-100% load (Slew Rate: 0.1A/μs)
Start-up with Capacitive Loads
4,000µF Max
Nominal Input Voltage
100-240Vac
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
DC Input Voltage Range
120-375Vdc
Input Current
2.2A typ. @ 115Vac, 1.2A typ. @ 230Vac
Efficiency at 100% load
89%typ.@115Vac, 90% typ.@ 230Vac
Max Inrush Current
20A typ. @ 115Vac, 40A typ. @ 230Vac
Leakage Current
< 0.25mA @ 264Vac
Dimensions
123.6 x 40 x 117.6 mm
4.87" x 1.57" x 4.63"
Unit Weight
0.54 kg (1.19 lb)
Case Chassis / Cover
SGCC / Aluminium
Indicator
Green LED (DC OK)
Cooling System
Convection
Operating Temperature
-20°C to +70°C
Storage Temperature
-40°C to +85°C
Power De-rating
-10°C to -20°C de-rate power by 2%/°C
> 40°C de-rate power by 1.67% / °C @ 115Vac
> 50°C de-rate power by 2.5% / °C @ 230Vac
< 100Vac de-rate power by 1% / Vac
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, 27, Half Sine Wave: 50G for duration of 11ms; 3 times per direction, 9 times in total
Shock (Operating)
IEC 60068-2-27, 27, Half Sine Wave: 10G for duration of 11ms; 1 time in X axis
Vibration Test (Non-Operating)
IEC 60068-2-6, Random: 5Hz to 500Hz; 2.09Grms; 20 min per axis for all X, Y, Z directions
Vibration (Operating)
IEC 60068-2-6, Sine Wave: 10Hz to 500Hz @ 19.6m/s² (2G peak); displacement of 0.35mm; 10 min per cycle, 60 min for X direction
Overvoltage
57.0V-67.2V, SELV Output, Latch Mode
Overload / Overcurrent
105-150% of rated load current, Continuous current
Over Temperature
Latch Mode
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of Protection
IP20
Protection Against Shock
Class I with Primary Earth connection
MTBF
Telcordia SR-332: > 700,000 hrs
I/P: 100Vac, O/P: 100% load, Ta: 25°C
Electrical Safety
TUV Bauart: EN 60950-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E131881)
CCC: GB4943.1
CB scheme: IEC 60950-1
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
Galvanic Isolation
Input to Output: 3.0KVac
Input to Ground: 2.0KVac
Output to Ground: 0.5KVac
Emission
(CE & RE)
Generic Standards: EN 61000-6-3, EN 61000-6-4
CISPR 32, EN 55032, EN 55011, FCC Title 47: Class B; GB9254.1
Immunity
Generic Standards: EN 61000-6-1, EN 61000-6-2, EN 55024
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A; GB17625.1
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3

Documents

Datasheet Uploaded on 24-Dec-2018 1.0 MB
.DXF Uploaded on 29-Jan-2016 4.7 MB
Manual Uploaded on 29-Jan-2016 2.8 MB
Mechanical Drawing Uploaded on 29-Jan-2016 42 KB
.STP Uploaded on 29-Jan-2016 2.9 MB
Image Uploaded on 03-Nov-2016 310 KB

Certificates

CB Uploaded on 29-Jan-2016 92 KB
CCC Uploaded on 29-Jan-2016 1.2 MB
CE Uploaded on 28-Mar-2017 122 KB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
TUV Uploaded on 29-Jan-2016 2.0 MB
UL Uploaded on 05-Apr-2019 835 KB

Related Products

CliQ M 24V 120W

DRM-24V120W1PN

-
Add to Comparison

Output Voltage

24V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

124 x 40 x 117 mm
4.88" x 1.57" x 4.61"

CliQ II 24V 120W

DRP-24V120W2BN

Add to Comparison

Output Voltage

24V

Output Current

5A

Input Voltage

0-550 Vac

Dimensions

124 x 40 x 117 mm
4.88" x 1.57" x 4.61"

CliQ II 48V 120W

DRP048V120W1BA

Add to Comparison

Output Voltage

48V

Output Current

2.5A

Input Voltage

0-0 Vac

Dimensions

121 x 50 x 123.1 mm
4.76" x 1.97" x 4.85"

Lyte 24V 120W

DRL-24V120W1AS

Add to Comparison

Output Voltage

24V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

123.6 x 40 x 117.6 mm
4.87" x 1.57" x 4.63"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT