DIN Rail Power Supply

CliQ II

24V 240W / DRP-24V240W2BN

Highlights & Features

  • Designed for single phase input 180-305Vac (for L-N) or 2 of 3-Phase system 2 x 180-550Vac (for L-L) or 254-780Vdc
  • Compact and corrosion resistant aluminium casing
  • Up to 90.0% efficiency and Power Boost of 120% for 3 seconds
  • Wide operating temperature range from -30°C to +70°C
  • Built-in constant current and hiccup during overload protection
  • Built-in DC OK Contact
  • Conformal coating on PCBAs to protect against common dust and chemical pollutants
Dimensions (L x W x D) : 
124 x 60 x 117 mm
4.88" x 2.36" x 4.61"
Unit Weight : 
0.81 kg (1.79 lb)
Nominal Output Voltage
24V
Output Current
10A
Output Voltage Adjustment Range
24-28Vdc
Output Power
240W
Line Regulation
< 0.5% typ. (@ 200-550Vac input, 100% load)
Load Regulation
< 1% typ. (@ 200-550Vac input, 0-100% load)
PARD
< 150mVpp @ -10°C and above
< 200mVpp @ below -10°C
Start-up Time
< 1,000ms @ nominal input (100% load)
Hold-up Time
>18ms @ 2 x 230Vac (100% load)
> 30ms @ 2 x 400Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 0-100% load
Start-up with Capacitive Loads
10,000µF Max
Nominal Input Voltage
2 x 200-500Vac (2-Phase)
200-277Vac (Single Phase)
Input Voltage Range
2 x 180-550Vac (2-Phase)
180-305Vac (Single Phase)
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
DC Input Voltage Range
254-780Vdc
Input Current
< 2.00A @ 2 x 230Vac, < 1.00A @ 2 x 400Vac
Efficiency at 100% load
> 90.0% @ 2 x 400Vac
Max Inrush Current
< 50A @ 2 x 200Vac & 2 x 500Vac
Leakage Current
< 3.5mA @ 500Vac
Max Power Dissipation
0% load: < 8.5W @ 2 x 200Vac, < 9.5W @ 2 x 500Vac
100% load: < 26.5W @ 2 x 200Vac, < 21.5W @ 2 x 500Vac
Dimensions
124 x 60 x 117 mm
4.88" x 2.36" x 4.61"
Unit Weight
0.81 kg (1.79 lb)
Case Chassis / Cover
Aluminium
Cooling System
Convection
Operating Temperature
-30°C to +70°C
Storage Temperature
-40°C to +85°C
Power De-rating
Vertical Mounting : > 50°C de-rate power by 2.25% / °C
Horizontal Mounting : > 30°C de-rate power by 2% / °C
Input Voltage : < 200Vac de-rate power by 0.5% / Vac
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
1 times per direction, 2 times in total
Vibration Test (Non-Operating)
IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak);
60 min per axis for all X, Y, Z direction
Operating Altitude
0 to 2,500 Meters (8,200 ft.) for ITE application (@ 50°C)
0 to 2,000 Meters (6,560 ft.) for Industrial application (@ 50°C)
Pollution Degree
2
Over Voltage Category
III: According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part)
Overvoltage
32V ±10%, SELV Output, Hiccup Mode,
Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 120-180% of rated load current, Constant current,
Hiccup Mode (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load,
Non-Latching (Auto-Recovery)
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of Protection
IP20
Protection Against Shock
Class I with PE* connection
MTBF
> 500,000 hrs. as per Telcordia SR-332 I/P: 2 x 200Vac & 500Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time
10 years (2 x 200Vac & 500Vac, 50% load @ 40°C)
Electrical Safety
SIQ Bauart: EN 60950-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
CB scheme: IEC 60950-1
CE
In conformance with EMC Directive 2014/30/EU (only AC input) and Low Voltage Directive 2014/35/EU
Galvanic Isolation
Input to Output : 4.0KVac
Input to Ground : 2.0KVac
Output to Ground : 1.5KVac
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA: CSA C22.2 No. 107.1-01 (File No. 181564)
Electrical Equipments of Machines
EN 60204-1 (over voltage category III)
Electrical Equipment for Use in Electrical Power Installations
IEC/EN 62477-1 / IEC 62103
Safety Entry Low Voltage
PELV (EN 60204-1), SELV (EN 60950-1)
Material and Parts
RoHS Directive 2011/65/EU Compliant (EN 50581)
Emission
CISPR 32, EN 55032, CISPR 11, EN 55011, FCC Title 47: Class B
Immunity
Generic Standards: EN 55024, EN 61000-6-2
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
Component Power Supply for General Use
EN 61204-3

Documents

Datasheet Uploaded on 01-Dec-2018 1.1 MB
.DXF Uploaded on 13-Jul-2015 163 KB
Mechanical Drawing Uploaded on 13-Jul-2015 37 KB
.STP Uploaded on 13-Jul-2015 3.7 MB
Manual Uploaded on 21-Dec-2016 1.3 MB
Image Uploaded on 03-Nov-2016 117 KB

Certificates

CB Uploaded on 21-Dec-2016 1.1 MB
CE Uploaded on 27-Mar-2017 47 KB
CSA Uploaded on 21-Jul-2015 76 KB
EAC Uploaded on 28-Jul-2016 1.2 MB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
SIQ Uploaded on 21-Dec-2016 1.1 MB
UL Uploaded on 13-Jul-2015 68 KB

Related Products

CliQ II 24V 240W

DRP024V240W1BA

Add to Comparison

Output Voltage

24V

Output Current

10A

Input Voltage

85-264 Vac

Dimensions

121 x 85 x 124.1 mm
4.76" x 3.35" x 4.89"

CliQ II 24V 240W

DRP024V240W3BA

Add to Comparison

Output Voltage

24V

Output Current

10A

Input Voltage

0-0 Vac

Dimensions

121 x 70 x 117.3 mm
4.76" x 2.76" x 4.62"

CliQ II 48V 240W

DRP048V240W1BA

Add to Comparison

Output Voltage

48V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

121 x 85 x 124.1 mm
4.76" x 3.35" x 4.89"

CliQ II 24V 480W

DRP024V480W1BA

Add to Comparison

Output Voltage

24V

Output Current

20A

Input Voltage

85-264 Vac

Dimensions

121 x 144 x 118.6 mm
4.76" x 5.67" x 4.67"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT