DIN Rail Power Supply

CliQ II

24V 60W / DRP024V060W1NY

Highlights & Features

  • Universal AC input voltage
  • Power will not de-rate for the entire input voltage range
  • NEC Class 2 and Limited Power Source (LPS) approvals
  • Conformal coating on PCBA to protect against chemical and dust pollutants
  • Hazardous Locations approval for ATEX and Class I, Div 2 (DRP024V060W1NY)


Dimensions (L x W x D) : 
120.6 x 32 x 119.3 mm
4.75" x 1.26" x 4.70"
Unit Weight : 
0.33 kg (0.73 lb)
Nominal Output Voltage
24V
Output Current
2.5A
Output Voltage Adjustment Range
22-28Vdc
Output Power
60W
Line Regulation
< 0.5% typ. (@ 85-264Vac input, 100% load)
Load Regulation
< 1% typ. (@ 85-264Vac input, 0-100% load)
Start-up Time
< 3000ms @ nominal input (100% load, 25°C)
Hold-up Time
> 20ms @ 115Vac (100% load)
> 125ms @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 85-264Vac input, 0-100% load
(Slew Rate: 0.1A/μS, 50% duty cycle @ 5Hz to 1KHz)
Start-up with Capacitive Loads
8,000µF Max
Nominal Input Voltage
100-240Vac
Input Voltage Range
85-264Vac 120-375Vdc
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
Input Current
< 1.50A @ 100Vac
Efficiency at 100% load
> 86.0% @ 115Vac,
> 87.0% @ 230Vac
Max Inrush Current
< 40A @ 115Vac,
< 80A @ 230Vac
Power Factor at 100% load
Conform to EN61000-3-2
Leakage Current
< 0.5mA @ 240Vac
Dimensions
120.6 x 32 x 119.3 mm
4.75" x 1.26" x 4.70"
Unit Weight
0.33 kg (0.73 lb)
Case Chassis / Cover
Plastic
Cooling System
Convection
Operating Temperature
-25°C to +80°C (Cold Start at -40°C)
Storage Temperature
-40°C to +85°C
Power De-rating
> 50°C de-rate power by 2.5% /°C
> 70°C de-rate power by 4% /°C
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 time per direction, 2 times in total
Vibration Test (Non-Operating)
IEC60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis for all X, Y, Z direction
Operating Altitude
0 to 2,500 Meters (8,200 ft.)
Pollution Degree
2
Over Voltage Category
III: According to EN 50178 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part)
Overvoltage
< 32V ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 120% & 150% of rated load current, Hicc-up Mode,Non-Latching (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit
Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of Protection
IP20
Protection Against Shock
Class I with Primary Earth connection
MTBF
> 800,000 hrs. as per Telcordia SR-332
I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
Electrical Safety
SIQ Bauart: EN 60950-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1
CB scheme: IEC 60950-1, Limited Power Source (LPS)
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU

For DRP024V060W1NY:
In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
Galvanic Isolation
Input to Output: 4.0 KVac
Input to Ground: 1.5KVac
Output to Ground: 1.5KVac
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA: CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
(For DRP024V060W1NY)
Hazardous Location: cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +80°C (> +50°C derating)]

EN 60079-0:2009, EN 60079-15:2010 [II 3G Ex nA nC IIC T4 Gc, Ta= -25°C to +80°C (> +50°C derating)]
II 3 G ATEX 2014/34/EU
(For DRP024V060W1NY)
Certificate No. EPS 12 ATEX 1 491 X
Electrical Equipments of Machines
EN 60204-1 (over voltage category III)
Electrical Equipment for Use in Electrical Power Installations
EN 62477-1 / IEC 62103
Safety Entry Low Voltage
PELV (EN60204), SELV (EN 60950-1)
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
CISPR 32, EN 55032, CISPR 11, EN 55011, FCC Title 47: Class B
Immunity
EN 55024, EN 61000-6-2
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
Component Power Supply for General Use
EN 61204-3

Documents

Datasheet Uploaded on 01-Dec-2018 1.3 MB
.DXF Uploaded on 13-Jul-2015 410 KB
Manual Uploaded on 22-May-2018 1.2 MB
Mechanical Drawing Uploaded on 13-Jul-2015 45 KB
.STP Uploaded on 21-Jul-2015 1.8 MB
Image Uploaded on 03-Nov-2016 153 KB

Certificates

ATEX Uploaded on 20-Nov-2017 1.0 MB
CB Uploaded on 25-Jul-2016 697 KB
CE Uploaded on 27-Mar-2017 47 KB
CSA Uploaded on 20-Nov-2017 168 KB
EAC Uploaded on 27-Mar-2019 1.1 MB
Hazloc Uploaded on 13-Jul-2015 153 KB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
SIQ Uploaded on 25-Jul-2016 711 KB
UL Uploaded on 28-May-2019 306 KB

Related Products

CliQ II 24V 60W

DRP024V060W1BA

Add to Comparison

Output Voltage

24V

Output Current

2.5A

Input Voltage

0-0 Vac

Dimensions

121 x 32 x 125 mm
4.76" x 1.26" x 4.92"

CliQ II 48V 60W

DRP048V060W1BA

Add to Comparison

Output Voltage

48V

Output Current

1.25A

Input Voltage

0-0 Vac

Dimensions

121 x 32 x 125 mm
4.76" x 1.26" x 4.92"

CliQ II 24V 60W

DRP024V060W3BA

Add to Comparison

Output Voltage

24V

Output Current

2.5A

Input Voltage

0-0 Vac

Dimensions

121 x 50 x 117.3 mm
4.76" x 1.97" x 4.62"

CliQ II 24V 91W

DRP-24V100W1NN

Add to Comparison

Output Voltage

24V

Output Current

3.8A

Input Voltage

0-0 Vac

Dimensions

124 x 40 x 124 mm
4.88" x 1.57" x 4.88"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT