DIN Rail Power Supply

CliQ

24V 60W / DRP024V060W3AA

Highlights & Features

  • Reliable design, with expected life of 10 years
  • Compact, rugged design for ease of handling and installation
  • Multiple connections to terminals allowed
  • Designed for Class I Div.2 Hazardous Locations environments
  • Meets worldwide safety requirements
  • RoHS Directive 2011/65/EU Compliant
  • Worldwide AC input range without power de-rating
  • Overvoltage / Overcurrent / Over Temperature Protections
  • 150% Power Boost (steady state peak load) for 3 seconds

 ** Discontinued Product **
 
Replaced by : DRP024V060W3BN


Dimensions (L x W x D) : 
121 x 70 x 118.5 mm
4.76" x 2.76" x 4.67"
Unit Weight : 
0.56 kg (1.23 lb)
Tags : ATEX ClassIDiv2
Nominal Output Voltage
24V
Output Current
2.5A
Output Voltage Adjustment Range
22-28Vdc
Output Power
60W
Line Regulation
< 0.5% typ. (@ 320-575Vac input, 100% load)
Load Regulation
< 1% typ. (@ 320-575Vac input, 0-100% load)
PARD
240mVpp @ 25°C
Start-up Time
< 1000ms @ nominal input (100% load)
Hold-up Time
> 30ms @ 3 x 400Vac,
> 60ms @ 3 x 500Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 0-100% load
Start-up with Capacitive Loads
10,000µF Max
Nominal Input Voltage
3 x 400-500Vac
Input Voltage Range
320-575Vac 450-800 Vdc
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
Input Current
< 0.30A @ 3 x 400Vac, < 0.20A @ 3 x 500Vac
Efficiency at 100% load
> 86.0% @ 3 x 400Vac & 3 x 500Vac
Max Inrush Current
< 30A @ 3 x 400Vac & 3 x 500Vac
Leakage Current
< 3.5mA @ 500Vac
Dimensions
121 x 70 x 118.5 mm
4.76" x 2.76" x 4.67"
Unit Weight
0.56 kg (1.23 lb)
Case Chassis / Cover
Aluminium
Cooling System
Convection
Operating Temperature
-20°C to +80°C
Storage Temperature
-25°C to +85°C
Power De-rating
> 50°C de-rate power by 2.5% / °C
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC60068-2-27, 30G (300m/S²) for a duration of 18ms, 3 time per direction, 18 times in total
Vibration Test (Non-Operating)
IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); 90 min per axis for all X, Y, Z direction
Overvoltage
< 32V ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit
Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Protection Against Shock
Class I with Primary Earth connection
MTBF
> 500,000 hrs. as per Telcordia SR-332
I/P: 3 x 400Vac, O/P: 100% load, Ta: 25°C
Electrical Safety
SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1, CB scheme to IEC 60950-1, CSA to UL 60950-1 and CSA C22.2 No. 60950-1 (File No. 181564)
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
Galvanic Isolation
Input to Output: 4.0KVac
Input to Ground: 2.0KVac,
Output to Ground: 1.5KVac
Industrial Control Equipment
UL listed to UL 508, CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta = -20°C to +80°C (> +50°C derating)]
EN 60079-0:2009, EN 60079-15:2010 [II 3G Ex nA IIC T4 Gc, Ta = -20°C to +80°C (> +50°C derating))
II 3 G ATEX 2014/34/EU
Certificate No. EPS 09 ATEX 1 215 X;
For IEC 60079-0, IEC 60079-15
Electrical Equipment for Use in Electrical Power Installations
EN 50178 / IEC 62103
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
CISPR 32, EN 55032, CISPR 11, EN 55011, FCC Title 47: Class B
Immunity
EN 55024
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3

Documents

Datasheet Uploaded on 27-Dec-2017 1.3 MB
.DXF Uploaded on 13-Jul-2015 107 KB
Manual Uploaded on 13-Jul-2015 1.7 MB
Mechanical Drawing Uploaded on 13-Jul-2015 54 KB
.STP Uploaded on 21-Jul-2015 1.5 MB
Image Uploaded on 03-Nov-2016 703 KB

Certificates

ATEX Uploaded on 21-Jul-2015 1.0 MB
CB Uploaded on 21-Jul-2015 1.2 MB
CE Uploaded on 13-Jul-2015 351 KB
CSA Uploaded on 13-Jul-2015 1.1 MB
EAC Uploaded on 27-Mar-2019 1.1 MB
Hazloc Uploaded on 13-Jul-2015 128 KB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
SIQ Uploaded on 13-Jul-2015 570 KB
UL Uploaded on 13-Jul-2015 68 KB

Related Products

CliQ 24V 60W

DRP024V060W1AA

ATEX ClassIDiv2
Add to Comparison

Output Voltage

24V

Output Current

2.5A

Input Voltage

0-0 Vac

Dimensions

121 x 32 x 120 mm
4.76" x 1.26" x 4.72"

CliQ 24V 60W

DRP024V060W1AZ

-
Add to Comparison

Output Voltage

24V

Output Current

2.5A

Input Voltage

0-0 Vac

Dimensions

120.6 x 32 x 113 mm
4.75" x 1.26" x 4.45"

CliQ 12V 60W

DRP012V060W1AA

ATEX ClassIDiv2
Add to Comparison

Output Voltage

12V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

121 x 32 x 120 mm
4.76" x 1.26" x 4.72"

CliQ 24V 120W

DRP024V120W1AA

ATEX ClassIDiv2
Add to Comparison

Output Voltage

24V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

121 x 50 x 118.7 mm
4.76" x 1.97" x 4.67"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT