DIN Rail Power Supply

CliQ

24V 120W / DRP024V120W1AA

Highlights & Features

  • Universal AC input voltage
  • Power will not de-rate for the entire input voltage range
  • Power Boost of 150% for 3 seconds
  • Full corrosion resistant aluminium chassis
  • SEMI F47 certified
  • Hazardous Locations approval to ATEX and Class I, Div 2 
Dimensions (L x W x D) : 
121 x 50 x 118.7 mm
4.76" x 1.97" x 4.67"
Unit Weight : 
0.54 kg (1.19 lb)
Tags : ATEX ClassIDiv2
Nominal Output Voltage
24V
Output Current
5A
Output Voltage Adjustment Range
22-28Vdc
Output Power
120W
Line Regulation
< 0.5% typ. (@ 85-264Vac input, 100% input)
Load Regulation
< 1% typ. (@ 85-264Vac input, 0-100% input)
PARD
< 240mVpp
Start-up Time
< 1000ms @ nominal input (100% load)
Hold-up Time
> 35ms @ 115Vac(100% load)
> 70ms @ 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 85-264Vac input, 5-100% load
(Slew Rate: 0.1A/μS, 50% duty cycle @ 5Hz to 1KHz)
Start-up with Capacitive Loads
10,000µF Max
Nominal Input Voltage
100-240Vac
Input Voltage Range
85-264Vac
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
Nominal DC Input Voltage
125-250Vdc
DC Input Voltage Range
120-375 Vdc
Input Current
< 1.40A @ 115Vac,
< 0.80A @ 230Vac
Efficiency at 100% load
> 86.0% @ 115Vac, > 87.0% @ 230Vac
Max Inrush Current
< 80A @ 115Vac,
No Damage @ 230Vac
Power Factor at 100% load
> 0.98 @ 115Vac,
> 0.87 @ 230Vac
Leakage Current
< 1mA @ 240Vac
Dimensions
121 x 50 x 118.7 mm
4.76" x 1.97" x 4.67"
Unit Weight
0.54 kg (1.19 lb)
Case Chassis / Cover
Aluminium
Cooling System
Convection
Operating Temperature
-20°C to +80°C
Storage Temperature
-25°C to +85°C
Power De-rating
Vertical: > 50°C de-rate power by 2.5% /°C
Horizontal: > 50°C de-rate power by 2.5% / °C, > 70°C de-rate power by 4% / °C
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,
3 times per direction, 18 times in total
Vibration Test (Non-Operating)
IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); 90 min per axis for all X, Y, Z direction
Overvoltage
32V +10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit
Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Protection Against Shock
Class I without Primary Earth connection
MTBF
> 500,000 hrs. as per Telcordia SR-332
I/P: 115Vac & 230Vac, O/P: 100% load, Ta: 25°C
Electrical Safety
SIQ Bauart: EN 60950-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (under alternate part number EOE12010002 of File No. E191395)
CSA: CSA C22.2 No. 60950-1 and UL 60950-1 (under alternate part number EOE12010002 of File No. 181564)
CB
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU

In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
Galvanic Isolation
Input to Output: 4.0KVac
Input to Ground: 1.5KVac
Output to Ground: 1.5KVac
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (under alternate part number EOE12010002 of File No. E315355)
CSA: CSA to CSA C22.2 No. 107.1-01 (under alternate part number EOE12010002 of File No. 181564)
Hazardous Location / ATEX
Hazardous Location: cCSAus to CSA C22.2 No. 213-M1987 and ANSI / ISA 12.12.01:2007; Class I, Division 2, Group A, B, C, D T4, Ta= -20°C to +80°C (> +50°C derating)
ATEX: EN 60079-0:2009, EN 60079-15:2010 (II 3G Ex nA IIC T4 Gc, Ta= -20°C to +80°C (> +50°C derating))
II 3 G ATEX 2014/34/EU
Certificate No. EPS 09 ATEX 1 215 X;
For IEC 60079-0, IEC 60079-15
Electrical Equipment for Use in Electrical Power Installations
EN 50178 / IEC 62103
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
CISPR32, EN55032, EN55011, FCC Title 47: Class B
Immunity
EN 55024, EN 61000-6-1
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3

Documents

Datasheet Uploaded on 01-Dec-2018 1.6 MB
.DXF Uploaded on 01-Feb-2016 135 KB
Manual Uploaded on 11-Nov-2016 1.3 MB
Mechanical Drawing Uploaded on 01-Feb-2016 60 KB
.STP Uploaded on 01-Feb-2016 1.6 MB
Image Uploaded on 03-Nov-2016 812 KB

Certificates

CB Uploaded on 22-Jul-2016 682 KB
CE Uploaded on 23-Mar-2017 47 KB
CSA Uploaded on 01-Feb-2016 138 KB
EAC Uploaded on 27-Mar-2019 1.1 MB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
SIQ Uploaded on 22-Jul-2016 634 KB
UL Uploaded on 12-Apr-2019 385 KB

Related Products

CliQ 24V 120W

DRP024V120W3AA

ATEX ClassIDiv2
Add to Comparison

Output Voltage

24V

Output Current

5A

Input Voltage

320-575 Vac

Dimensions

121 x 70 x 118.4 mm
4.76" x 2.76" x 4.66"

CliQ 24V 240W

DRP024V240W1AA

ATEX ClassIDiv2
Add to Comparison

Output Voltage

24V

Output Current

10A

Input Voltage

0-0 Vac

Dimensions

121 x 85 x 118.5 mm
4.76" x 3.35" x 4.67"

CliQ 24V 240W

DRP024V240W3AA

ATEX ClassIDiv2
Add to Comparison

Output Voltage

24V

Output Current

10A

Input Voltage

320-575 Vac

Dimensions

121 x 85 x 120.5 mm
4.76" x 3.35" x 4.74"

CliQ II 24V 120W

DRP024V120W1BA

Add to Comparison

Output Voltage

24V

Output Current

5A

Input Voltage

85-264 Vac

Dimensions

121 x 50 x 123.1 mm
4.76" x 1.97" x 4.85"