DIN Rail Power Supply

CliQ II

24V 120W / DRP024V120W1BA

Highlights & Features

  • Universal AC input voltage
  • Power will not de-rate for the entire input voltage range
  • Power Boost of 150% for 5 seconds
  • Full corrosion resistant aluminium chassis
  • Conformal coating on PCBA to protect against common dust and chemical pollutants
  • Hazardous Locations approval to ATEX and Class I, Div 2 (DRP024V120W1BA)


Dimensions (L x W x D) : 
121 x 50 x 123.1 mm
4.76" x 1.97" x 4.85"
Unit Weight : 
0.72 kg (1.59 lb)
Nominal Output Voltage
24V
Output Current
5A
Output Voltage Adjustment Range
24-28Vdc
Output Power
120W
Line Regulation
< 0.5% typ. (@ 85-264Vac input, 100% load)
Load Regulation
< 1% typ. (@ 85-264Vac input, 0-100% load)
Start-up Time
< 1000ms @ nominal input (100% load, 25°C)
Hold-up Time
> 20ms @ 115Vac,
> 115ms @ 230Vac (100% load, 25°C)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 0-100% load
Start-up with Capacitive Loads
10,000µF Max
Nominal Input Voltage
100-240Vac
Input Voltage Range
85-264Vac 120-375Vdc
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
Nominal DC Input Voltage
120-375Vdc
Input Current
< 2.20A @ 115Vac, < 1.10A @ 230Vac
Efficiency at 100% load
> 89.0% @ 115Vac,
> 90.0% @ 230Vac
Max Inrush Current
< 35A @ 115Vac & 230Vac
Power Factor at 100% load
Conform with EN61000-3-2
Leakage Current
< 1mA @ 240Vac
Dimensions
121 x 50 x 123.1 mm
4.76" x 1.97" x 4.85"
Unit Weight
0.72 kg (1.59 lb)
Case Chassis / Cover
Aluminium
Indicator
Green LED (DC OK)
Cooling System
Convection
Operating Temperature
-25°C to +80°C (Cold Start at -40°C)
Storage Temperature
-40°C to +85°C
Power De-rating
> 50°C de-rate power by 2.5% / °C
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 time per direction, 2 times in total
Vibration Test (Non-Operating)
IEC60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis for all X, Y, Z direction
Operating Altitude
0 to 2,500 Meters
Pollution Degree
2
Overvoltage
< 32V ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 150% of rated load current, Hicc-up Mode,Non-Latching (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit
Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of Protection
IP20
Protection Against Shock
Class I with Primary Earth connection
MTBF
> 800,000 hrs. as per Telcordia SR-332
I/P: 115Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
Electrical Safety
SIQ to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), CB scheme to IEC 60950-1
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
For DRP024V120W1BA: In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
Galvanic Isolation
Input to Output 4.0KVac
Input to Ground 1.5KVac
Output to Ground 1.5KVac
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355), CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
(For DRP024V120W1BA)
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2011 [Class I, Division 2, Group A, B, C, D T4, Ta= -25°C to +80°C (> +50°C derating)]
EN 60079-0:2009, EN 60079-15:2010 [ II 3G Ex nA nC IIC T4 Gc, Ta= -25°C to +80°C (> +50°C derating)]
II 3 G ATEX 2014/34/EU
(For DRP024V120W1BA)
Certificate No. EPS 12 ATEX 1 491 X
Electrical Equipment for Use in Electrical Power Installations
EN 50178 / IEC 62103
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
CISPR 32, EN 55032, CISPR 11, EN 55011, FCC Title 47: Class B
Immunity
EN 55024, EN 61000-6-1, EN 61000-6-2
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
Component Power Supply for General Use
EN 61204-3

Documents

Datasheet Uploaded on 01-Dec-2018 1.5 MB
.DXF Uploaded on 13-Jul-2015 198 KB
Manual Uploaded on 11-Nov-2016 1.5 MB
Mechanical Drawing Uploaded on 13-Jul-2015 57 KB
.STP Uploaded on 21-Jul-2015 2.0 MB
Image Uploaded on 03-Nov-2016 801 KB

Certificates

ATEX Uploaded on 20-Nov-2017 1.0 MB
CB Uploaded on 25-Jul-2016 701 KB
CCC Uploaded on 07-May-2018 691 KB
CE Uploaded on 27-Mar-2017 47 KB
CSA Uploaded on 20-Nov-2017 168 KB
EAC Uploaded on 27-Mar-2019 1.1 MB
Hazloc Uploaded on 13-Jul-2015 153 KB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
SIQ Uploaded on 25-Jul-2016 702 KB
UL Uploaded on 13-Jul-2015 68 KB

Related Products

CliQ II 24V 120W

DRP-24V120W2BN

Add to Comparison

Output Voltage

24V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

124 x 40 x 117 mm
4.88" x 1.57" x 4.61"

CliQ II 24V 120W

DRP024V120W3BA

Add to Comparison

Output Voltage

24V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

121 x 50 x 117.3 mm
4.76" x 1.97" x 4.62"

CliQ II 48V 120W

DRP048V120W1BA

Add to Comparison

Output Voltage

48V

Output Current

2.5A

Input Voltage

0-0 Vac

Dimensions

121 x 50 x 123.1 mm
4.76" x 1.97" x 4.85"

CliQ II 24V 240W

DRP024V240W1BA

Add to Comparison

Output Voltage

24V

Output Current

10A

Input Voltage

85-264 Vac

Dimensions

121 x 85 x 124.1 mm
4.76" x 3.35" x 4.89"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT