DIN Rail Power Supply

CliQ II

24V 240W / DRP024V240W3BA

Highlights & Features

  • Universal AC input voltage range 3 x 320-600Vac without power de-rating
  • Able to operate at 2 x 360-600Vac without power de-rating even when one phase input is lost
  • Power Boost of 150% for 5 seconds
  • Full corrosion resistance Aluminium chassis
  • Conforms to harmonic current IEC/EN 61000-3-2, Class A
  • Conformal coating on PCBA to protect against chemical and dust pollutants
  • Hazardous Locations approval to ATEX and Class I, Div 2 available as option


Dimensions (L x W x D) : 
121 x 70 x 117.3 mm
4.76" x 2.76" x 4.62"
Unit Weight : 
0.89 kg (1.96 lb)
Nominal Output Voltage
24V
Output Current
10A
Output Voltage Adjustment Range
24-28Vdc
Output Power
240W
Line Regulation
< 0.5% typ. (@ 320-600Vac input, 100% load)
Load Regulation
< 1% typ. (@ 320-600Vac input, 0-100% load)
PARD
< 150mVpp
Start-up Time
< 1,000ms @ nominal input (100% load)
Hold-up Time
> 20ms @ 3 x 400Vac,
> 40ms @ 3 x 500Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 0-100% load
Start-up with Capacitive Loads
10,000µF Max
Nominal Input Voltage
3 x 400-500Vac
Input Voltage Range
3 x 320-600Vac
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
DC Input Voltage Range
450-800Vdc
Input Current
< 0.75A @ 3 x 400Vac,
< 0.65A @ 3 x 500Vac
Efficiency at 100% load
> 92.0% @ 3 x 400Vac & 3 x 500Vac
Max Inrush Current
< 40A @ 3 x 400Vac & 3 x 500Vac
Power Factor at 100% load
Conform with EN61000-3-2
Leakage Current
< 3.5mA @ 500Vac
Dimensions
121 x 70 x 117.3 mm
4.76" x 2.76" x 4.62"
Unit Weight
0.89 kg (1.96 lb)
Case Chassis / Cover
Aluminium
Cooling System
Convection
Operating Temperature
-25°C to +80°C
Storage Temperature
-25°C to +85°C
Power De-rating
> 50°C de-rate power by 2.5% / °C ,
>70°C de-rate power by 5% / °C
Operating Humidity
0 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms, 1 time per direction, 2 times in total
Vibration Test (Non-Operating)
IEC 60068-2-6, 10Hz to 500Hz @ 30m/S² (3G peak); 60 min per axis for all X, Y, Z direction
Overvoltage
< 32V, ±10%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Protection Against Shock
Class I with Primary Earth connection
MTBF
> 500,000 hrs. as per Telcordia SR-332
Electrical Safety
SIQ Bauart: EN 60950-1
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
CB scheme: IEC 60950-1
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
For DRP024V240W3BA:
In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
Galvanic Isolation
Input to Output 4.0KVac
Input to Ground 2.0KVac
Output to Ground 1.5KVac
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
CSA: CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
(For DRP024V240W3BA)
cCSAus: CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2007 [Class I, Division 2, Group A, B, C, D T4, Ta = -25°C to +80°C for Vertical (> +50°C derating) and -25°C to +70°C for Horizontal (> +40°C derating)]
II 3 G ATEX 2014/34/EU
(For DRP024V240W3BA)
ATEX: EN 60079-0:2012, EN 60079-15:2010 [II 3G Ex nA IIC T4 Gc, Ta= -25°C to +80°C for Vertical (> +50°C derating) and -25°C to +70°C for Horizontal (> +40°C derating)]
Certificate No. EPS 13 ATEX 1 575 X
Electrical Equipment for Use in Electrical Power Installations
EN 50178 / IEC 62103
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
(CE & RE)
CISPR 32, EN 55032, CISPR 11, EN 55011, FCC Title 47: Class B
Immunity
EN 55024, EN 61000-6-2
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3
Component Power Supply for General Use
EN 61204-3

Documents

Datasheet Uploaded on 21-Dec-2018 1.3 MB
.DXF Uploaded on 13-Jul-2015 139 KB
Manual Uploaded on 11-Nov-2016 1.4 MB
Mechanical Drawing Uploaded on 13-Jul-2015 35 KB
.STP Uploaded on 13-Jul-2015 1.6 MB
Image Uploaded on 03-Nov-2016 60 KB

Certificates

ATEX Uploaded on 20-Nov-2017 714 KB
CB Uploaded on 25-Jul-2016 698 KB
CE Uploaded on 27-Mar-2017 47 KB
CSA Uploaded on 20-Nov-2017 148 KB
EAC Uploaded on 27-Mar-2019 1.1 MB
Hazloc Uploaded on 14-Oct-2016 101 KB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
SIQ Uploaded on 25-Jul-2016 709 KB
UL Uploaded on 28-May-2019 375 KB

Related Products

CliQ II 24V 240W

DRP-24V240W2BN

Add to Comparison

Output Voltage

24V

Output Current

10A

Input Voltage

0-0 Vac

Dimensions

124 x 60 x 117 mm
4.88" x 2.36" x 4.61"

CliQ II 24V 240W

DRP024V240W1BA

Add to Comparison

Output Voltage

24V

Output Current

10A

Input Voltage

85-264 Vac

Dimensions

121 x 85 x 124.1 mm
4.76" x 3.35" x 4.89"

CliQ II 48V 240W

DRP048V240W1BA

Add to Comparison

Output Voltage

48V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

121 x 85 x 124.1 mm
4.76" x 3.35" x 4.89"

CliQ II 24V 480W

DRP024V480W3BA

Add to Comparison

Output Voltage

24V

Output Current

20A

Input Voltage

0-0 Vac

Dimensions

121 x 140 x 117.3 mm
4.76" x 5.51" x 4.62"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT