Panel Mount Power Supply

PMF

24V 320W / PMF-24V320WCGB

Highlights & Features

  • Universal AC input voltage
  • Built-in active PFC and fan speed control
  • Full corrosion resistant aluminium chassis
  • Conforms to harmonic current IEC/EN 61000-3-2, Class A and Class D
  • Cold start -20°C at 100% load (320W)
  • Remote ON/OFF is available as an option 


Dimensions (L x W x D) : 
215 x 115 x 50 mm
8.46" x 4.53" x 1.97"
Unit Weight : 
0.84 kg (1.85 lb)
Nominal Output Voltage
24V
Output Current
13.3A
Output Voltage Adjustment Range
21.6-26.4Vdc
Output Power
320W
Line Regulation
± 0.2% typ. (@ 115Vac & 230Vac)
Load Regulation
± 1.0% typ. (@ 115Vac & 230Vac)
PARD
< 150mVpp @ 25°C
< 300mVpp @ -10°C
Start-up Time
2500ms typ. @ 115Vac,
800ms typ. @ 230Vac (100% load)
Hold-up Time
20ms typ. @ 115Vac & 230Vac
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% (2.4V pk-pk) @ 115Vac & 230Vac (0-100% load)
Start-up with Capacitive Loads
8,000µF Max
Nominal Input Voltage
100-240Vac
Input Voltage Range
85-264Vac
Input Frequency Range
47-63Hz
Input Current
< 5.00A @ 115Vac,
< 2.50A @ 230Vac
Efficiency at 100% load
87.0% typ. @ 230Vac
Power Factor at 100% load
0.98 typ. @ 115Vac,
0.95 typ. @ 230Vac
Leakage Current
< 1mA @ 240Vac
Dimensions
215 x 115 x 50 mm
8.46" x 4.53" x 1.97"
Unit Weight
0.84 kg (1.85 lb)
Case Chassis / Cover
Aluminium
Cooling System
Forced Cooling
Operating Temperature
-10°C to +70°C (Cold start at -20°C)
Storage Temperature
-25°C to +85°C
Power De-rating
> 50°C de-rate power by 2.5% / °C
< 100Vac de-rate power by 1.33% / 1V
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine: 50G for a duration of 11ms, 3 shocks for each 3 directions
Vibration Test (Non-Operating)
IEC 60068-2-6, Random: 5Hz to 500Hz (2.09Grms); 20 min per axis for all X, Y, Z direction
Overvoltage
27.6-32.4V, Latch Mode (AC power is recycled)
Overload / Overcurrent
105-150%, Hiccup Mode, Non-Latching (Auto-Recovery)
Over Temperature
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
Protection Against Shock
Class I with PE(Primary Earth) connection
MTBF
> 700,000 hrs. as per Telcordia SR-332
I/P: 100Vac, O/P: 100% load, Ta: 35°C
CE
In conformance with EMC Directive 2004/108/EC and Low Voltage Directive 2006/95/EC
Emission
CISPR 22, EN 55022, FCC Title 47: Class B
Immunity
EN 55024
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A and Class D
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3

Documents

Datasheet Uploaded on 13-Nov-2018 2.0 MB
.DXF Uploaded on 27-Apr-2017 385 KB
Manual Uploaded on 13-Jul-2015 593 KB
Mechanical Drawing Uploaded on 13-Jul-2015 46 KB
.STP Uploaded on 13-Jul-2015 2.3 MB
Image Uploaded on 03-Nov-2016 72 KB

Certificates

CB Uploaded on 24-Aug-2016 689 KB
CCC Uploaded on 24-Aug-2016 1.7 MB
CE Uploaded on 07-Jun-2017 121 KB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
TUV Uploaded on 13-Jul-2015 1.2 MB
UL Uploaded on 05-Apr-2019 245 KB

Related Products

PMF 24V 320W

PMF-24V320WCGB

Add to Comparison

Output Voltage

24V

Output Current

13.3A

Input Voltage

0-0 Vac

Dimensions

215 x 115 x 50 mm
8.46" x 4.53" x 1.97"

PMF 4V 231W

PMF-4V320WCGB

Add to Comparison

Output Voltage

4V

Output Current

55A

Input Voltage

0-0 Vac

Dimensions

215 x 115 x 50 mm
8.46" x 4.53" x 1.97"

PMF 5V 275W

PMF-5V320WCGB

Add to Comparison

Output Voltage

5V

Output Current

55A

Input Voltage

0-0 Vac

Dimensions

215 x 115 x 50 mm
8.46" x 4.53" x 1.97"

PMF 24V 202W

PMF-24V200WCGB

Add to Comparison

Output Voltage

24V

Output Current

8.4A

Input Voltage

0-0 Vac

Dimensions

190 x 93 x 50 mm
7.48" x 3.66" x 1.97"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT