Panel Mount Power Supply

PMH

24V 150W / PMH-24V150WCBS

Highlights & Features

  • Household appliance approvals IEC/EN 60335-1, IEC/EN 61558-1 and IEC/EN 61558-2-16
  • Universal AC input voltage
  • Full power from -20°C to +50°C operation @ 5000m or 16400 ft. altitude
  • Full corrosion resistant aluminium casing
  • High MTBF > 700,000 hrs as per Telcordia SR-332
  • Versatile connector options available: IP20, Front Face and Harness connectors


Dimensions (L x W x D) : 
178 x 97 x 38 mm
7.01" x 3.82" x 1.50"
Unit Weight : 
0.56 kg (1.23 lb)
Nominal Output Voltage
24V
Output Current
6.25A
Output Voltage Adjustment Range
22-28Vdc
Output Power
150W
Line Regulation
< 0.5% (@ 85-264Vac input, 100% load)
Load Regulation
< 0.5% (@ 85-264Vac input, 0-100% load)
PARD
< 100mVpp
Start-up Time
100Vac: < 1800ms (@ -20°C to 70°C) & < 2500ms (@ < -20°C to -30°C)
240Vac: < 1000ms (@ -30°C to 70°C)
Hold-up Time
> 40ms @ 115Vac, > 50ms 230Vac (100% load)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 85-264Vac input, 0-100% load
(Slew Rate: 0.1A/μS, 50% duty cycle @ 5Hz to 100Hz)
Start-up with Capacitive Loads
8,000μF Max
(@ > -20°C, 85-264Vac input & @ ≤ -20°C, 100-264Vac input)
Rise Time
< 35ms @ nominal input (100% load)
Nominal Input Voltage
100-240Vac
Input Voltage Range
85-264Vac
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
DC Input Voltage Range
120-375Vdc
Input Current
< 1.60A @ 115Vac, < 0.90A @ 230Vac
Efficiency at 100% load
> 89.0% @ 115Vac, > 91.0% @ 230Vac
Max Inrush Current
< 30A @ 115Vac, < 60A @ 230Vac
Power Factor at 100% load
> 0.98 @ 115Vac, > 0.89 @ 230Vac
Leakage Current
< 1.2mA @ 240Vac
Max Power Dissipation
0% load: < 0.08W @ 115Vac & < 1.0W @ 230Vac
100% load: 18.5W typ. @ 115Vac & 15.8W typ. @ 230Vac
Dimensions
178 x 97 x 38 mm
7.01" x 3.82" x 1.50"
Unit Weight
0.56 kg (1.23 lb)
Case Chassis / Cover
Aluminium
Indicator
Green LED (DC OK)
Cooling System
Convection
Operating Temperature
-30°C to +70°C
Storage Temperature
-30°C to +85°C
Power De-rating
-20°C to -30°C de-rate power by 2.0% / °C
> 50°C de-rate power by 2.5% / °C
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms,1 times per direction, 2 times in total
Vibration Test (Non-Operating)
IEC 60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); displacement of 0.35mm; 20 min per axis for all X, Y, Z direction
Operating Altitude
0 to 5,000 Meters (16,400 ft.)
Pollution Degree
2
Bump Test (Operating)
IEC 60068-2-29, 10G (100m/S²) for a duration of 11ms,1000 times per direction, 6000 times in total
Over Voltage Category
II
Overvoltage
28.8-35.2V range, Hiccup Mode,
Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 120% of rated load current, Hiccup Mode, Non-Latching (Auto recovery)
Over Temperature
< 75°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-recovery)
Short Circuit
Hiccup Mode, Non-Latching (Auto-recovery when the fault is removed)
Degree of Protection
IP20
Protection Against Shock
Class I with Primary Earth connection
MTBF
> 700,000 hrs. as per Telcordia SR-332
I/P: 115Vac, O/P: 100% load, Ta: 25°C
Expected Cap Life Time
10 years (115Vac & 230Vac, 50% load @ 40°C)
Electrical Safety
SIQ Bauart: EN 60950-1, EN 60335-1, EN 61558-1, EN 61558-2-16
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
CB scheme: IEC 60950-1, IEC 60335-1, IEC 61558-1, IEC 61558-2-16
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EC
Galvanic Isolation
Input to Output : 4.5KVac
Input to Ground : 1.5KVac

Output to Ground :
Output non-isolated to PE (common pins connect to PE)(PMH-24V150WC☐A, PMH-24V150WC☐J, PMH-24V150WC☐L, PMH-24V150WC☐H)
1.5KVdc (Output isolated to PE) (PMH-24V150WC☐S, PMH-24V150WC☐U, PMH-24V150WC☐V, PMH-24V150WC☐T)
Safety Entry Low Voltage
Output non-isolated to PE: PELV (EN 60335), SELV (EN 60950)
Output isolated to PE: SELV (EN 60335), SELV (EN 60950)
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
(CE & RE)
CISPR 32, EN 55032, FCC Title 47: Class B,
EN 55014-1, EN 61000-6-3
Immunity
EN 55024, EN 61000-6-1, EN 55014-2
Harmonic Current Emissions
IEC/EN 61000-3-2, Class A
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3

Documents

Datasheet Uploaded on 27-Nov-2018 1.3 MB
.DXF Uploaded on 10-Dec-2015 1.5 MB
Manual Uploaded on 27-Mar-2019 1.3 MB
Mechanical Drawing Uploaded on 21-May-2018 342 KB
.STP Uploaded on 10-Dec-2015 1.6 MB
Image Uploaded on 03-Nov-2016 397 KB

Certificates

CB Uploaded on 24-Aug-2016 1.3 MB
CE Uploaded on 09-Dec-2015 387 KB
EAC Uploaded on 27-Mar-2019 1.1 MB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
SIQ Uploaded on 24-Aug-2016 2.2 MB
UL Uploaded on 01-Oct-2015 68 KB

Related Products

PMH 24V 200W

PMH-24V200WCBA

Add to Comparison

Output Voltage

24V

Output Current

8.33A

Input Voltage

85-264 Vac

Dimensions

190 x 97 x 38 mm
7.48" x 3.82" x 1.50"

PMC 24V 150W

PMC-24V150W1AA

Add to Comparison

Output Voltage

24V

Output Current

6.25A

Input Voltage

0-0 Vac

Dimensions

178 x 97 x 38 mm
7.01" x 3.82" x 1.50"

PMC 24V 150W

PMC-24V150W2AA

Add to Comparison

Output Voltage

24V

Output Current

6.25A

Input Voltage

0-0 Vac

Dimensions

178 x 97 x 38 mm
7.01" x 3.82" x 1.50"

PMC 24V 150W

PMC-24V150W1BA

Add to Comparison

Output Voltage

24V

Output Current

6.25A

Input Voltage

0-0 Vac

Dimensions

178 x 97 x 38 mm
7.01" x 3.82" x 1.50"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT