Click the link below to download the file.
Get your files as below link
Dowload link
24V
960W
40A
3 x 320-575Vac (3-Phase) or 2 x 380-575Vac (2-Phase)
124 x 110 x 128.6 mm
4.88” x 4.33” x 5.06”
2.3kg (5.07 lb)
24V
960W
40A
3 x 320-575Vac (3-Phase) or 2 x 380-575Vac (2-Phase)
124 x 110 x 128.6 mm
4.88” x 4.33” x 5.06”
2.3kg (5.07 lb)
Output Current
40A
|
Output Voltage
24V
|
Output Voltage Range
24-28Vdc
|
Output Voltage Adjustment Range
24-28Vdc
|
Output Power
960W
|
Output Current Adjustment Range
|
Max Output Voltage
|
Buffering Time
-
|
Line Regulation
10mV (@ 3 x 320-575Vac input, 100% load)
|
Load Regulation
80mV (@ 3 x 320-575Vac input, 0-100% load)
|
PARD
100mVpp Max.
|
Start-up Time
1,000ms @ 24V, 40A
|
Hold-up Time
50.4ms @ 24V, 20A
|
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 1.5-100% load
|
Start-up with Capacitive Loads
40,000μF
|
Remote ON/OFF
-
|
Protective Device
-
|
Voltage Drop Between Input and Output
-
|
Residual Ripple/PARD (20MHz)
-
|
Residual Ripple
-
|
Max. Power
-
|
Ripple & Noise
-
|
LED System Voltage Range in CC Mode
-
|
Rise Time
65ms
|
Power Boost Duration
5 seconds Typ.
7 seconds Max. |
Power Boost Recovery Time
17 seconds Typ.
|
Nominal Input Voltage
3 x 400-500Vac
|
Input Voltage Range
3 x 320-575Vac (3-Phase) or 2 x 380-575Vac (2-Phase)
|
Max Input Voltage
-
|
Nominal Input Frequency
50-60Hz
|
Input Frequency Range
47-63Hz
|
Nominal DC Input Voltage
|
DC Input Voltage Range
450-800Vdc
|
Input Current
1.53A @ 24V, 40A
|
Input Power (Standby Mode)
-
|
Efficiency at 100% load
95.75% @ 24V, 40A
|
Max Inrush Current
14.2A
|
Charging Time
-
|
Power Factor at 100% load
0.95 @ 24V, 40A
|
Leakage Current
< 0.62mA / 0.64mA @ 3 x400Vac, 50Hz, TN/TT / IT system
|
Nominal Current
-
|
Total Harmonic Distortion
-
|
Max Power Dissipation
-
|
Efficiency @ 10% load
-
|
Case Chassis / Cover
Aluminium
|
|
Indicator
Green LED DC OK
Red LED Overload |
|
Cooling System
Convection
|
|
Input Terminal
4 Pins (Rated 600V/35A)
|
|
Output Terminal
4 Pins (Rated 300V/65A)
|
|
Signal Terminal
5 Pins (Rated 300V/12A)
|
|
Noise Sound Pressure Level (SPL)
< 25dBA
|
|
Input/Output Terminal
-
|
|
Signal
-
|
|
Mounting Rail
Standard TS35 DIN Rail in accordance with EN 60715
|
|
Wire
-
|
|
Protection Structure
-
|
|
Terminal
-
|
|
Unit Weight
2.3kg (5.07 lb)
|
Dimensions
124 x 110 x
128.6 mm
4.88” x 4.33” x 5.06” |
Vibration (Operating)
-
|
Shock Test (Operating)
-
|
Operating Temperature
-25°C to +70°C (Cold start -40°C)
|
Storage Temperature
-40°C to +85°C
|
Power De-rating
Vertical Mounting: 3-Phase : > 60°C de-rate power by 2.5% / °C 2-Phase: > 50°C de-rate power by 2.5% / °C
Horizontal Mounting : 3-Phase: > 40°C de-rate power by 1.67% / °C 2-Phase: > 40°C de-rate power by 2% / °C |
Operating Humidity
5 to 95% RH (Non-Condensing)
|
Shock Test (Non-Operating)
IEC 60068-2-27, Half Sine Wave: 30G for a duration of 18ms; 3 times per direction, 6 times in total
|
Vibration (Non-Operating)
IEC 60068-2-6, Sine Wave: 10-500Hz; 3G peak; displacement of 0.35mm; 60 min per axis for all X, Y, Z directions
|
Storage Humidity
-
|
Operating Altitude
OVC III : 0 to 2,500 Meters (8,200 ft.)
OVC II : 2,500 to 6,000 Meters (19,680 ft.), 0 to 5,000 Meters (16,400 ft.), 0 to 3,000 Meters (9,840 ft.) |
Pollution Degree
2
|
Bump Test (Operating)
IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
|
Over Voltage Category
-
|
Corrosion
-
|
Overvoltage
< 32V, SELV Output, Hiccup Mode, Non-Latching (Auto- Recovery)
|
Overload / Overcurrent
150-200% of rated load current, Constant current, Hiccup Mode (Auto-Recovery)
|
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
|
Short Circuit
Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed)
|
Reverse Polarity Protection
-
|
Degree of Protection
IP20
|
Protection Against Shock
Class I with Primary Earth connection
|
Input Polarity Protection
-
|
Battery Polarity Protection
-
|
Wrong Battery Voltage Protection
-
|
Deep Discharge Protection
-
|
Overload
-
|
Overcurrent
-
|
Internal Fuse
-
|
Insufficient Input Voltage Protection
-
|
MTBF
568,300 hrs. as per Telcordia SR-332
I/P: 3 x 400Vac, O/P: 24V, 40A, Ta: 25°C |
Expected Cap Life Time
368,800 hrs. @ I/P: 3 x 400Vac, O/P: 24V, 20A, Ta: 25°C
|
Safety Certificate
-
|
Electrical Safety
SIQ Bauart: EN 62368-1, EN 61558-1, EN 61558-2-16, EN 61010-1, EN 61010-2-201
UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395) UL 62368-1 and CSA C22.2 No. 62368-1 (File No. E191395) CB scheme: IEC 60950-1, IEC 62368-1, IEC 61558-1, IEC 61558-2-16, IEC 61010-1, IEC 61010-2-201 UKCA: BS EN 62368-1, BS EN 61558-1, BS EN 61558-2-16, BS EN 61010-1, BS EN 61010-2-201 |
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
|
Medical Safety
-
|
Galvanic Isolation
-
|
Industrial Control Equipment
UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
|
Hazardous Location / ATEX
-
|
II 3 G ATEX 2014/34/EU
-
|
Electrical Equipments of Machines
EN/BS EN 60204-1 (over voltage category III)
|
Electrical Equipment for Use in Electrical Power Installations
IEC/EN/BS EN 62477-1 / IEC 62103
|
Safety Entry Low Voltage
SELV (IEC 60950-1)
|
Maritime
DNV GL: Germanischer Lloyd classified
ABS: American Bureau for Shipping PDA Environmental category: C, EMC2 |
Material and Parts
-
|
Isolation Resistance
> 5MOhm Input to Output, 500Vdc
|
PE Resistance
< 0.1Ohm
|
UKCA
In conformance with Electrical Equipment (Safety) Regulations 2016 No. 1011 and The Electromagnetic Compatibility Regulations 2016 No. 1091
|
Certificates for Other Countries
-
|
BIS
-
|
KC
-
|
Electrical Equipment for Measurement, Control, and Laboratory Use
-
|
ITE Safety
-
|
SIL3
-
|
Emission
(CE & RE)
Generic Standards: EN/BS EN 61000-6-3 CISPR 32, EN/BS EN 55032, CISPR 11, EN/BS EN 55011, FCC Title 47: Class B |
Immunity
Generic Standards: EN/BS EN 55024, EN/BS EN 55035, EN 61000-6-2
|
Harmonic Current Emissions
IEC/EN/BS EN 61000-3-2, Class A
|
Voltage Fluctuation and Flicker
IEC/EN/BS EN 61000-3-3
|
ESD Immunity
-
|
Radiated Immunity
-
|
EFT
-
|
Surge
-
|
Conducted Immunity
-
|
Magnetic Field
-
|
Voltage Dips
-
|
Component Power Supply for General Use
EN/BS EN 61204-3
|
24V
480W
20A
3 x 320-575 Vac
48V
120W
2.5A
90-264 Vac
24V
480W
20A
90-264 Vac
48V
240W
5A
90-264 Vac
Subscribe to DeltaPSU newsletter and be the first to know about our new product releases and industry knowledge. Read our Privacy Policy.
DeltaPSU will use the information you provide on this form to be in touch with you.