DIN Rail Power Supply

CliQ III

24V 240W / DRP-24V240W1CAN

Highlights & Features

  • Universal AC input voltage range
  • Built-in constant current circuit for charging application
  • High efficiency of up to 94% at 230Vac
  • Power Boost of 150% for 5 seconds
  • Advanced Power Boost (APB) of 200% for 50ms
  • SEMI F47 compliance at 120Vac
  • Extreme low temperature cold start at -40°C
  • Built-in DC OK Contact and LED indicator for DC OK
  • Conformal coating on PCBA to protect against common dust and chemical pollutants


    Dimensions (L x W x D) : 
    124 x 60 x 117 mm
    4.88" x 2.36" x 4.61"
    Unit Weight : 
    0.84 kg (1.85 lb)
    Nominal Output Voltage
    24V
    Output Current
    10A
    Output Voltage Adjustment Range
    24-28Vdc
    Output Power
    240W
    Line Regulation
    0.5% (@ 88-264Vac input, 100% load)
    Load Regulation
    1% (@ 88-264Vac input, 0-100% load)
    PARD
    100mVpp Max.
    Start-up Time
    1,000ms Max. @ 24V, 10A
    Hold-up Time
    24ms Typ. @ 24V, 10A
    20ms min. @ 24V, 10A
    Dynamic Response (Overshoot & Undershoot O/P Voltage)
    ± 5% @ 0-100% load
    Start-up with Capacitive Loads
    10,000µF Max.
    Rise Time
    60ms Max. @ 24V, 10A
    Nominal Input Voltage
    100-240Vac
    Input Voltage Range
    100-264Vac (Continuously operating)
    88-100Vac (With power de-rating)
    Nominal Input Frequency
    50-60Hz
    Input Frequency Range
    47-63Hz
    DC Input Voltage Range
    100-375Vdc (Continuously operating, with safety approval according to IEC/EN/UL 60950-1)
    88-100Vdc (With power de-rating)
    Input Current
    2.27A Typ. @ 115 Vac, 1.19A typ. @ 230Vac
    Efficiency at 100% load
    92.70% Typ. @ 115Vac, 94.48% Typ. @ 230Vac
    Max Inrush Current
    (Cold Start)
    11.0A Typ. @ 115Vac, 24.4A Typ. @ 230Vac, 33A Max. @ 115Vac, 65A Max. @ 230Vac
    Power Factor at 100% load
    0.99 Typ. @ 115Vac, 0.93 Typ. @ 230Vac, 0.99 Min. @ 115Vac, 0.93 Min. @ 230Vac
    Leakage Current
    (Enclosure to Neutral)
    < 0.25mA / 0.80mA: 110Vac, 50Hz, TN/TT system / IT system
    < 0.38mA / 1.00mA: 132Vac, 50Hz, TN/TT system / IT system
    < 0.74mA / 2.00mA: 264Vac, 50Hz, TN/TT system / IT system
    Max Power Dissipation
    At 24V, 0A: 3.54W Typ. @ 115Vac, 2.90W Typ. @ 230Vac, 6.0W Max. @ 115Vac, 6.0W Max. @ 230Vac
    At 24V, 10A: 18.97W Typ. @ 115Vac, 14.05W Typ. @ 230Vac, 21.0W Max. @ 115Vac, 16.0W Max. @ 230Vac
    Dimensions
    124 x 60 x 117 mm
    4.88" x 2.36" x 4.61"
    Unit Weight
    0.84 kg (1.85 lb)
    Case Chassis / Cover
    Aluminium
    Indicator
    Green LED (DC OK)
    Cooling System
    Convection
    Operating Temperature
    -25°C to +70°C (Cold start -40°C)
    Storage Temperature
    -40°C to +85°C
    Power De-rating
    Vertical Mounting: > 60°C de-rate power by 2.5% / °C
    Horizontal Mounting: > 40°C de-rate power by 2.5% / °C
    Input Voltage:
    AC input
    < 100Vac de-rate power by 0.83% / V
    DC input
    < 100Vdc de-rate power by 1.67% / V
    Operating Humidity
    5 to 95% RH (Non-Condensing)
    Shock Test (Non-Operating)
    IEC 60068-2-27, Half Sine Wave: 30G for a duration of 18ms; 3 times per direction, 9 times in total
    Vibration Test (Non-Operating)
    IEC 60068-2-6, Sine Wave: 10-500Hz; 3G peak; displacement of 0.35mm; 60 min per axis for all X, Y, Z directions
    Operating Altitude
    0 to 5,000 Meters (16,400 ft.)
    Pollution Degree
    2
    Bump Test (Operating)
    IEC 60068-2-29, Half Sine Wave: 10G for a duration of 11ms, 1,000 times per direction, 6,000 times in total
    Over Voltage Category
    III (operating altitude 2,500 Meters)
    II (operating altitude 5,000 Meters)
    According to IEC/EN 62477-1 / EN 60204-1 (clearance and creepage distances) and IEC 62103 (safety part)
    Overvoltage
    28.8 - 35.2V, SELV Output, Hiccup Mode, Non-Latching (Auto-Recovery)
    Overload / Overcurrent
    125 – 170% of rated load current, Constant current, Hiccup Mode (Auto-Recovery)
    Over Temperature
    < 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
    Short Circuit
    Hiccup Mode, Non-Latching (Auto-Recovery when the fault is removed): Load impedance ≤ 100mOhm
    Degree of Protection
    IP20
    Protection Against Shock
    Class I with Primary Earth connection
    MTBF
    1,366,200 hrs.: I/P: 115Vac, O/P: 24V, 10A, Ta: 25°C
    767,400 hrs.: I/P: 115Vac, O/P: 24V, 10A, Ta: 40°C
    Expected Cap Life Time
    O/P: 24V, 10A, Ta: 25°C: 87,600hrs. @ 115Vac & 230Vac
    O/P: 24V, 5A, Ta: 40°C: 87,600hrs. @ 115Vac & 230Vac
    O/P: 24V, 10A, Ta: 60°C: 29,000hrs. @ 115Vac, 40,000hrs. @ 230Vac
    O/P: 24V, 7.5A, Ta: 60°C: 45,900hrs.@ 115Vac, 62,300hrs. @ 230Vac
    Electrical Safety
    SIQ Bauart: EN 60950-1
    UL/cUL recognized: UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395)
    CB scheme: IEC 60950-1
    CE
    In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
    Galvanic Isolation
    Input to Output: 4.0KVac
    Input to Ground: 2.0KVac
    Input to DC OK relay contact: 4.0KVac
    Output to Ground: 1.5KVac
    Output to DC OK relay contact: 0.5KVac
    DC OK relay contact to PE: 1.5KVac
    Industrial Control Equipment
    UL/cUL listed: UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355)
    Electrical Equipments of Machines
    EN 60204-1 (over voltage category III)
    Electrical Equipment for Use in Electrical Power Installations
    IEC/EN 62477-1 / IEC 62103
    Safety Entry Low Voltage
    PELV (EN 60204-1), SELV (EN 60950-1)
    Material and Parts
    RoHS Directive 2011/65/EU Compliant (EN 50581)
    PE Resistance
    < 0.1Ohm
    Emission
    (CE & RE)
    Generic Standards: EN 61000-6-3
    CISPR 32, EN 55032, CISPR 11, EN 55011, FCC Title 47: Class B
    Immunity
    Generic Standards: EN 55024, EN 61000-6-2
    Harmonic Current Emissions
    IEC/EN 61000-3-2, Class A
    Voltage Fluctuation and Flicker
    IEC/EN 61000-3-3
    Component Power Supply for General Use
    EN 61204-3

    Documents

    Datasheet Uploaded on 14-Dec-2018 1.1 MB
    .DXF Uploaded on 08-Aug-2018 144 KB
    Manual Uploaded on 01-Aug-2018 974 KB
    Mechanical Drawing Uploaded on 31-Jul-2018 141 KB
    .STP Uploaded on 08-Aug-2018 2.4 MB
    Image Uploaded on 31-Jul-2018 377 KB

    Certificates

    CB Uploaded on 31-Jul-2018 681 KB
    CE Uploaded on 31-Jul-2018 210 KB
    EAC Uploaded on 27-Mar-2019 1.1 MB
    REACH Uploaded on 18-Dec-2018 545 KB
    RoHS Uploaded on 18-Dec-2018 380 KB
    SIQ Uploaded on 31-Jul-2018 744 KB
    UL Uploaded on 20-Dec-2017 68 KB

    Related Products

    CliQ 24V 240W

    DRP024V240W1AA

    ATEX ClassIDiv2
    Add to Comparison

    Output Voltage

    24V

    Output Current

    10A

    Input Voltage

    0-0 Vac

    Dimensions

    121 x 85 x 118.5 mm
    4.76" x 3.35" x 4.67"

    CliQ II 24V 240W

    DRP-24V240W2BN

    Add to Comparison

    Output Voltage

    24V

    Output Current

    10A

    Input Voltage

    0-550 Vac

    Dimensions

    124 x 60 x 117 mm
    4.88" x 2.36" x 4.61"

    CliQ II 24V 240W

    DRP024V240W1BA

    Add to Comparison

    Output Voltage

    24V

    Output Current

    10A

    Input Voltage

    85-264 Vac

    Dimensions

    121 x 85 x 124.1 mm
    4.76" x 3.35" x 4.89"

    CliQ 24V 240W

    DRP024V240W3AA

    ATEX ClassIDiv2
    Add to Comparison

    Output Voltage

    24V

    Output Current

    10A

    Input Voltage

    320-575 Vac

    Dimensions

    121 x 85 x 120.5 mm
    4.76" x 3.35" x 4.74"