DIN Rail Power Supply

CliQ

12V 30W / DRP012V030W1AY

Highlights & Features

  • Universal AC input voltage
  • Power will not de-rate for the entire input voltage range
  • Power Boost of 150% for 3 seconds
  • Conformal coating on PCBAs to protect against common dust and chemical pollutants
  • Hazardous Locations approval to ATEX and Class I, Div 2 (DRP012V030W1AY)
  • Overvoltage / Overcurrent / Over Temperature / Short Circuit Protections


Dimensions (L x W x D) : 
100 x 32 x 100.6 mm
3.94" x 1.26" x 3.96"
Unit Weight : 
0.20 kg (0.44 lb)
Nominal Output Voltage
12V
Output Current
2.5A
Output Voltage Adjustment Range
11-14Vdc
Output Power
30W
Line Regulation
< 0.5% typ. (@ 85-264 Vac input, 100% input)
Load Regulation
<1% typ. (@ 85-264 Vac input, 0-100% input)
Start-up Time
< 2500ms @ nominal input (100% load, 25°C)
Hold-up Time
> 22ms @ 115Vac,
> 110ms @ 230Vac (100% load, 25°C)
Dynamic Response (Overshoot & Undershoot O/P Voltage)
± 5% @ 10-100% load
Start-up with Capacitive Loads
6,600µF Max
Nominal Input Voltage
100-240Vac
Input Voltage Range
85-264Vac 120-375Vdc
Nominal Input Frequency
50-60Hz
Input Frequency Range
47-63Hz
Input Current
< 0.70A @ 115Vac,
< 0.42A @ 230Vac
Efficiency at 100% load
> 85.0% @ 115Vac & 230Vac
Max Inrush Current
< 30A @ 115Vac,
< 65A @ 230Vac
Power Factor at 100% load
Conform to EN61000-3-2
Leakage Current
< 1mA @ 240Vac
Dimensions
100 x 32 x 100.6 mm
3.94" x 1.26" x 3.96"
Unit Weight
0.20 kg (0.44 lb)
Case Chassis / Cover
Plastic
Cooling System
Convection
Operating Temperature
-20°C to +80°C
Storage Temperature
-25°C to +85°C
Power De-rating
> 50°C de-rate power by 2.5% /°C,
> 70°C de-rate power by 4% /°C
Operating Humidity
5 to 95% RH (Non-Condensing)
Shock Test (Non-Operating)
IEC 60068-2-27, 30G (300m/S²) for a duration of 18ms, 3 times per direction, 18 times in total
Vibration Test (Non-Operating)
IEC60068-2-6, 10Hz to 150Hz @ 50m/S² (5G peak); 90 min per axis for all X, Y, Z direction
Pollution Degree
2
Overvoltage
16V +10% / -5%, SELV Output, Hicc-up Mode, Non-Latching (Auto-Recovery)
Overload / Overcurrent
> 150% of rated load current, Hicc-up Mode, Non-Latching (Auto-Recovery)
Over Temperature
< 80°C Surrounding Air Temperature @ 100% load, Non-Latching (Auto-Recovery)
Short Circuit
Hicc-up Mode, Non-Latching (Auto-Recovery when the fault is removed)
Degree of Protection
IPX0
Protection Against Shock
Class I without Primary Earth connection
MTBF
> 1,000,000 hrs. as per Telcordia SR-332
Electrical Safety
TUV to EN 60950-1, UL/cUL recognized to UL 60950-1 and CSA C22.2 No. 60950-1 (File No. E191395), CB scheme to IEC 60950-1
CE
In conformance with EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU

For DRP012V030W1AY:
In conformance with Equipment for explosive atmospheres (ATEX) directive 2014/34/EU
Galvanic Isolation
Input to Output: 4.0KVac,
Input to Ground: 1.5KVac,
Output to Ground: 1.5KVac
Industrial Control Equipment
UL/cUL listed to UL 508 and CSA C22.2 No. 107.1-01 (File No. E315355),
CSA to CSA C22.2 No. 107.1-01 (File No. 181564)
Hazardous Location / ATEX
cCSAus to CSA C22.2 No. 213-M1987, ANSI / ISA 12.12.01:2011
Class I, Division 2, Group A, B, C, D T4, Ta= -20°C to +80°C (> +50°C derating)

EN 60079-0:2012, EN 60079-15:2010 (II 3G Ex nA IIC T4 Gc, Ta= -20°C to +80°C (> +50°C derating))
II 3 G ATEX 2014/34/EU
Certificate No. EPS 12 ATEX 1 491 X
Electrical Equipment for Use in Electrical Power Installations
EN 50178 / IEC 62103
Material and Parts
RoHS Directive 2011/65/EU Compliant
Emission
CISPR 32, EN 55032, CISPR 11, EN 55011, FCC Title 47: Class B
Immunity
EN 55024, EN 61000-6-1, EN 61000-6-2
Voltage Fluctuation and Flicker
IEC/EN 61000-3-3

Documents

Datasheet Uploaded on 30-Nov-2018 1.3 MB
.DXF Uploaded on 13-Jul-2015 463 KB
Manual Uploaded on 11-Nov-2016 1.7 MB
Mechanical Drawing Uploaded on 13-Jul-2015 44 KB
.STP Uploaded on 21-Jul-2015 1.5 MB
Image Uploaded on 03-Nov-2016 453 KB

Certificates

ATEX Uploaded on 20-Nov-2017 1.0 MB
CB Uploaded on 22-Jul-2016 140 KB
CE Uploaded on 27-Apr-2017 47 KB
CSA Uploaded on 20-Nov-2017 168 KB
EAC Uploaded on 27-Mar-2019 1.1 MB
Hazloc Uploaded on 13-Jul-2015 153 KB
REACH Uploaded on 18-Dec-2018 545 KB
RoHS Uploaded on 18-Dec-2018 380 KB
TUV Uploaded on 22-Jul-2016 607 KB
UL Uploaded on 12-Apr-2019 603 KB

Related Products

CliQ 12V 15W

DRP012V015W1AY

Add to Comparison

Output Voltage

12V

Output Current

1.25A

Input Voltage

0-0 Vac

Dimensions

100 x 32 x 100.6 mm
3.94" x 1.26" x 3.96"

CliQ 12V 60W

DRP012V060W1AA

ATEX ClassIDiv2
Add to Comparison

Output Voltage

12V

Output Current

5A

Input Voltage

0-0 Vac

Dimensions

121 x 32 x 120 mm
4.76" x 1.26" x 4.72"

CliQ 12V 100W

DRP012V100W1AA

ATEX ClassIDiv2
Add to Comparison

Output Voltage

12V

Output Current

8.33A

Input Voltage

0-0 Vac

Dimensions

121 x 50 x 118.7 mm
4.76" x 1.97" x 4.67"

CliQ 24V 48W

DRP-24V48W1AZ

-
Add to Comparison

Output Voltage

24V

Output Current

1A

Input Voltage

0-0 Vac

Dimensions

100 x 32 x 100.6 mm
3.94" x 1.26" x 3.96"
We use cookies to provide the best user experience for those who visit our website. By using this website you agree to the placement of cookies and our Privacy Policy . ACCEPT